Plan Review Notes
Plan Review Notes For Permit 01110595
Permit Number 01110595
Review Stop M
Sequence Number 1
Notes
Date Text
2001-11-21 00:00:00******************DENIED****************
  
  
 PLEASE PROVIDE MANUFACTURER SUBMITTAL
 DATA FOR HOOD SCRUBBER.
  
 PLAN SHEET M-2, GREASE HOOD DUCT WRAP
 SEE DETAIL ON DWG. M-3/13.NO SUCH
 PLAN SUBMITTED.
  
 AS PER 1997 SMC 505.5.1, CLEANOUT
 OPENINGS ARE REQUIRED FOR EACH CHANGE
 OF DIRECTION.PLEASE SHOW LOCATIONS OF
 ALL CLEANOUTS.
  
 NOTE - GREASE DUCT SHALL HAVE A MINIMUM
 SLOPE OF 1 INCH PER FOOT.
  
 SHOW COMPLIANCE WITH NFPA 96 SECTION 6-3
 AND 6-3.1.
  