| 2001-11-21 00:00:00 | ******************DENIED**************** | | | | | | | | | PLEASE PROVIDE MANUFACTURER SUBMITTAL | | | DATA FOR HOOD SCRUBBER. | | | | | | PLAN SHEET M-2, GREASE HOOD DUCT WRAP | | | SEE DETAIL ON DWG. M-3/13.NO SUCH | | | PLAN SUBMITTED. | | | | | | AS PER 1997 SMC 505.5.1, CLEANOUT | | | OPENINGS ARE REQUIRED FOR EACH CHANGE | | | OF DIRECTION.PLEASE SHOW LOCATIONS OF | | | ALL CLEANOUTS. | | | | | | NOTE - GREASE DUCT SHALL HAVE A MINIMUM | | | SLOPE OF 1 INCH PER FOOT. | | | | | | SHOW COMPLIANCE WITH NFPA 96 SECTION 6-3 | | | AND 6-3.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|