| Plan Review Notes For Permit 01110595 |
| Permit Number |
01110595 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-11-21 00:00:00 | 1) PLEASE PROVIDE PRODUCT APPROVALS FOR | | | FAN SCRUBBER UNIT. PLEASE PROVIDE ALL | | | APPLICABLE DATA FOR SCRUBBER UNIT. | | | 2) NFPA 96 REQUIRES THAT NO DOWNGRADING | | | OF EXHUAST DUCT IS TO OCCUR AFTER THE | | | PROPOSED FAN SCRUBBER UNIT. ALSO THIS | | | CODE REQUIRES A FIRE SUPPRESSION SYSTEM | | | FOR THIS EQUIPMENT. PLEASE SEE NFPA 96 | | | FOR DETAILS. SEPARATE PLANS AND PERMITS | | | WILL BE REQUIRED FOR THIS FIRE | | | SUPPRESSION SYSTEM. IT APPEARS THAT F5 | | | HAS BEEN REMOVED FROM FAN SCHEDULE ON | | | PAGE M-5. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|