Plan Review Notes
Plan Review Notes For Permit 01110574
Permit Number 01110574
Review Stop P
Sequence Number 1
Notes
Date Text
2001-11-20 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) SPC SEC 407.2.2 REQUIRED FACILITIES
 SHALL BE DIRECTLY ACCESSIBLE TO THE PUB-
 LIC THROUGH DIRECT OPENINGS OR CORRIDORS
 FROM THE AREA OR AREAS THEY ARE INTENDED
 TO SERVE. DOOR OPENING NOT ACCEPTABLE.
 PAGE A-1
  
 2) PAGE A-1, OFFICE DOORS TO OFFICE
 SHALL NOT OPEN INTO CLEAR FLOOR SPACE OF
 SINK PER FACBC SEC 4.22.2
  
 3) PAGE A-1, PER SPC TABLE 407 1 DRINK-
 ING FOUNTAIN IS REQUIRED. D.F SHALL COM-
 PLY WITH FACBC SEC 4.15. IF A SINGLE D.
 F. IS USED PROVISIONS SHALL BE MADE FOR
 THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING PER FACBC SEC 4.1.3(10).
  
 4) PAGE M-1, WATER PIPING DIAGRAM. IF
 W/HEATER HAS EMERGENCY PAN, IT SHALL
 HAVE A 1" DRAIN LINE. AIR CHAMBERS ARE
 QUICK FIX AND REQUIRE ACCESS PANELS AND
 SHALL BE RECHARGEABLE PER SPC SEC 607.8.
 3. WATER HAMMER ARRESTORS CAN BE INSTALL
 ED WITH OUT ACCESS PANELS.
  
 REVIEW BY KENSTEVENS
 (561) 659-8096 EXT 8377