| Plan Review Notes For Permit 01110574 |
| Permit Number |
01110574 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-11-19 00:00:00 | ******************* UNSAT ************* | | | | | | 1)NOTE: PLEASE SHOW LOAD CALCUALTIONS, | | | PER 220-3/220-13/220-11 | | | PLEASE SHOW ALL CONTINUOUS LOADS AT | | | 125%. (LIGHTING) ETC. | | | | | | 2)NOTE: PLEASE NOTE MISSING SHOW WINDOW | | | OUTLETS PER 210-62 LOADS PER 220-12A | | | | | | 3)NOTE: PLEASE NOTE MISSING SIGN CIRCUIT | | | PER 600-5. | | | | | | PLEASE USBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|