Plan Review Notes
Plan Review Notes For Permit 01110574
Permit Number 01110574
Review Stop E
Sequence Number 1
Notes
Date Text
2001-11-19 00:00:00******************* UNSAT *************
  
 1)NOTE: PLEASE SHOW LOAD CALCUALTIONS,
 PER 220-3/220-13/220-11
 PLEASE SHOW ALL CONTINUOUS LOADS AT
 125%. (LIGHTING) ETC.
  
 2)NOTE: PLEASE NOTE MISSING SHOW WINDOW
 OUTLETS PER 210-62 LOADS PER 220-12A
  
 3)NOTE: PLEASE NOTE MISSING SIGN CIRCUIT
 PER 600-5.
  
 PLEASE USBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372