2002-06-12 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE SCHEDULE FOR PANEL
 "B" NEEDS TO HAVE LOAD/OCP/WIRE SIZE
 CORRELATE. PLEASE NOTE 20KW SHOWN FOR
 #12 W/20A OCP.
 PLEASE ALSO CLARIFY LOAD SHOWN FOR
 XFMR AS #4? MISPRINT?
  
 2)NOTE: PLEASE SHOW CONTINOUS LOADS AT
 125%.
  
 3)NOTE: PLEASE CLARIFY WHERE COND UNIT
 IS FED FROM. 480V PANEL SHOWS AHU BUT
 NOT COND UNIT??
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
 PLEASE NOTE, THIS IS THE FIRST TIME A
 RISER DIAGRAM HAS BEEN SUBMITTED FOR
 REVIEW. PLEASE SUBMIT ASAP FOR REVIEW.