| 2002-02-20 00:00:00 | ********************DENIED************** | | | | | | | | | 1.PROVIDE INFORMATION ON THE RETURN | | | AIR GRILLE IN THE DOOR.IS THIS FOR | | | AIR TRANSFER & DOES THE STORAGE ROOM | | | ALSO HAVE A RETURN AIR GRILLE IN THE | | | CEILING?AS PER 1997 SMC 609.1, A | | | ROOM SHALL NOT BE USED AS AN | | | INTEGRAL PART OF A DUCT SYSTEM OR | | | PLENUM.SUCH CHAMBERS SHALL NOT BE | | | USED FOR STORAGE OR OCCUPATIONAL | | | PURPOSES. | | | | | | 2.PROVIDE OUTSIDE AIR CALCULATIONS AS | | | PER ASHRAE 62-89. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096, | | | EXT. 8388. |
|