| Plan Review Notes For Permit 01110542 |
| Permit Number |
01110542 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-11-19 00:00:00 | ***************** UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE MISSING SHOW WINDOW | | | OUTLETS PER 210-62 LOAD PER 220-12A. | | | | | | 2)NOTE: PLEASE NOTE MISSING EXITS/EM LTS | | | PLEASE SHOW. | | | | | | 3)NOTE: PLEASE SHOW LOAD CALCULATIONS, | | | PER 220-3/220-11/220-13 ETC. | | | PLEASE NOTE THAT ALL CONTINUOUS LOADS | | | ARE TO BE SHOWN AT 125% 230-42/215-3 | | | | | | 4)NOTE: PLEASE CLARIFY 100A OCP FOR | | | #6 AWG ON A/C UNIT. AT 20KW LOAD? | | | | | | 5)NOTE: PLEASE CLARIFY METHOD OF EQUIP- | | | -MENT GROUND BETWEEN MAIN DISCONNECT AND | | | PANEL. PLEASE SIZE CONDCUTOR PER 250-122 | | | | | | 6)NOTE: PLEASE CLARIFY SWITCHING FOR | | | LIGHTS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | | | | ***NOTE*** | | | | | | NEED TO PROVIDE CONTRACT FOR COMPLETE | | | SCOPE OF WORK TO INCLUDE ALL LABOR AND | | | MATERIALS. NEED TO VERIFY VALUE ON THE | | | APPLICATION. 104.7.5 OF PALM BEACH | | | COUNTY AND CITY WIDE ADMIN. CODE. |
|