2001-11-19 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASE NOTE MISSING SHOW WINDOW
 OUTLETS PER 210-62 LOAD PER 220-12A.
  
 2)NOTE: PLEASE NOTE MISSING EXITS/EM LTS
 PLEASE SHOW.
  
 3)NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PER 220-3/220-11/220-13 ETC.
 PLEASE NOTE THAT ALL CONTINUOUS LOADS
 ARE TO BE SHOWN AT 125% 230-42/215-3
  
 4)NOTE: PLEASE CLARIFY 100A OCP FOR
 #6 AWG ON A/C UNIT. AT 20KW LOAD?
  
 5)NOTE: PLEASE CLARIFY METHOD OF EQUIP-
 -MENT GROUND BETWEEN MAIN DISCONNECT AND
 PANEL. PLEASE SIZE CONDCUTOR PER 250-122
  
 6)NOTE: PLEASE CLARIFY SWITCHING FOR
 LIGHTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
 ***NOTE***
  
 NEED TO PROVIDE CONTRACT FOR COMPLETE
 SCOPE OF WORK TO INCLUDE ALL LABOR AND
 MATERIALS. NEED TO VERIFY VALUE ON THE
 APPLICATION. 104.7.5 OF PALM BEACH
 COUNTY AND CITY WIDE ADMIN. CODE.