| 2001-11-20 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT# 01110542 |
| | 477 S ROSEMARY/175 |
| | CONT:INSIDE OUTFITTERS |
| | TEL: (954) 561-5262 |
| | |
| | SBC= 1997 STANDARD BUILDING CODE |
| | SBC*= AMENDMENTS STANDARD BUILDING CODE |
| | FL ACCES CODE= FLORIDA ACCESSIBILITY |
| | CODE |
| | |
| | 1)- FL ENERGY CALS. SECTION 400 |
| | 2)- SBC 1606.4.1*/ 1707.4.1* ALL GLAZED |
| | OPENINGS WILL REQUIRE PRODUCT TESTING |
| | REPORTS FOR LARGE MISSLE IMPACT RESIS- |
| | TANCE. (2) COPIES OF EITHER SBCCI OR |
| | DADE COUNTY PRODUCT TESTING REPORTS ARE |
| | ACCEPTED. |
| | 3)- PLANS DO NOT INDICATE ELEVATIONS- |
| | CUT SECTIONS THROUGH TENANT SEPERATION |
| | WALLS. |
| | 4)- PLANS DO NOT INDICATE SOFFITS NOR |
| | CEILING DROPS, FASTENING SCHEDULE NOR |
| | FRAMING SPACING. |
| | 5)- PLANS DO NOT GIVE THE MINIMUM BUILD- |
| | ING TYPE, IF FIRE SPRINKLERED? |
| | 6)- THE FINISH WALL SCHEDULE IS MISSING, |
| | SBC TABLE 803.3 MINIMUM INTERIOR FINISH |
| | SCHEDULE. |
| | 7)- PUBLIC RESTROOMS 1204.2 REQUIRE A |
| | NON-ABSORBANT MATERIAL ON FLOORAND 4'-0" |
| | HIGH ON THE SIDE WALLS. |
| | 8)- FL ACCES CODE 4.5 FLOOR SURFACES |
| | ALONG ACCESIBLE ROUTES AND IN ACCESIBLE |
| | ROOMS AND SPACES INCLUDING FLOORS, WALKS |
| | AND RAMPS SHALL BE STABLE, FIRM AND |
| | SLIP-RESISTANT. ADDAAG A-5 A STATIC |
| | COEFFICIENT OF FRICTION 0.6 ON ACCESIBLE |
| | ROUTES AND 0.8 ON RAMPS. |
| | |
| | PLANS ARE INADEQUITE TO DO A THOROUGH PL |
| | AN REVIEW WITH. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561) 659-8096 X8412 |