Plan Review Notes
Plan Review Notes For Permit 01110542
Permit Number 01110542
Review Stop B
Sequence Number 1
Notes
Date Text
2001-11-20 00:00:00BUILDING PLAN REVIEW
 PERMIT# 01110542
 477 S ROSEMARY/175
 CONT:INSIDE OUTFITTERS
 TEL: (954) 561-5262
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS STANDARD BUILDING CODE
 FL ACCES CODE= FLORIDA ACCESSIBILITY
 CODE
  
 1)- FL ENERGY CALS. SECTION 400
 2)- SBC 1606.4.1*/ 1707.4.1* ALL GLAZED
 OPENINGS WILL REQUIRE PRODUCT TESTING
 REPORTS FOR LARGE MISSLE IMPACT RESIS-
 TANCE. (2) COPIES OF EITHER SBCCI OR
 DADE COUNTY PRODUCT TESTING REPORTS ARE
 ACCEPTED.
 3)- PLANS DO NOT INDICATE ELEVATIONS-
 CUT SECTIONS THROUGH TENANT SEPERATION
 WALLS.
 4)- PLANS DO NOT INDICATE SOFFITS NOR
 CEILING DROPS, FASTENING SCHEDULE NOR
 FRAMING SPACING.
 5)- PLANS DO NOT GIVE THE MINIMUM BUILD-
 ING TYPE, IF FIRE SPRINKLERED?
 6)- THE FINISH WALL SCHEDULE IS MISSING,
 SBC TABLE 803.3 MINIMUM INTERIOR FINISH
 SCHEDULE.
 7)- PUBLIC RESTROOMS 1204.2 REQUIRE A
 NON-ABSORBANT MATERIAL ON FLOORAND 4'-0"
 HIGH ON THE SIDE WALLS.
 8)- FL ACCES CODE 4.5 FLOOR SURFACES
 ALONG ACCESIBLE ROUTES AND IN ACCESIBLE
 ROOMS AND SPACES INCLUDING FLOORS, WALKS
 AND RAMPS SHALL BE STABLE, FIRM AND
 SLIP-RESISTANT. ADDAAG A-5 A STATIC
 COEFFICIENT OF FRICTION 0.6 ON ACCESIBLE
 ROUTES AND 0.8 ON RAMPS.
  
 PLANS ARE INADEQUITE TO DO A THOROUGH PL
 AN REVIEW WITH.