2001-11-20 00:00:00BUILDING PLAN REVIEW
 PERMIT# 01110459
 2201 45TH ST
 COLUMBIA HOSPITAL/ NURSES STATION
 2ND/ 3RD FLOOR
 ARELLANO CONSTRUCTION
 TEL: (305) 994-9901
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS/ STANDARD BUILDING CODE
  
 1)- SHEET A-3 WALL PRIORITY LEGAND:
 SBC 704.2.1.4. CORRIDOR PARTITIONS,
 SMOKESTOP PARTITIONS, HORIZONTAL EXIT
 PARTITIONS, EXIT ENCLOSURES AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY & PERMAN-
 ETLY IDENTIFIED WITH SIGNS OR STENCILING
 : FIRE & SMOKE BARRIER PROTECT ALL OPEN-
 INGS.
  
 2)- SHEET A-3 SBC 705.4.1 PROTECTION OF
 PENETRATIONS THROUGH FIRE RATED AND NON-
 FIRE RATED ASSEMBLIES SHALL COMPLY WITH
 705.5(FIRE RATED WALLS) & 705.6 PENETRA-
 TIONS OF HORIZONTAL ASSEMBLIES (FLOORS,
 FLOOR/ CEILING ASSEMBLIES OR A ROOF
 CEILING ASSEMBLIES). REQUIRE A UL LIST-
 ING.
  
 3)- SHEET F-0 IS MISSING THE MINIMUM
 INTERIOR FINISH CLASSIFICATION SBC
 TABLE 803.3.
  
 4)- FL ACCESSIBILITY CODE 4.5. FLOOR
 SURFACES ALONG ACCESSIBLE ROUTES AND IN
 ACCESSIBLE ROOMS, SPACES INCLUDING RAMPS
 AND STAIRS SHALL BE STABLE, FIRM AND
 SLIP RESISTANT. ADDAAG A-5 A STATIC
 COEFFICIENT OF FRICTION OF 0.6 FOR
 ACCESSIBLE ROUTES & 0.8 FOR RAMPS.
  
 5)- TYPE I TYPE II BUILDINGS REQUIRE
 FIRE SPRINKLER PLANS AS PART OF THE
 BUILDING PERMITED PLANS. (2 COPIES).
 FIRE SPRINKLER PERMIT WILL REQUIRE A
 SEPERATE PERMIT, PLANS WITH ASSOCIATED
 FEES.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X8412