| 2001-11-20 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT# 01110459 |
| | 2201 45TH ST |
| | COLUMBIA HOSPITAL/ NURSES STATION |
| | 2ND/ 3RD FLOOR |
| | ARELLANO CONSTRUCTION |
| | TEL: (305) 994-9901 |
| | |
| | SBC= 1997 STANDARD BUILDING CODE |
| | SBC*= AMENDMENTS/ STANDARD BUILDING CODE |
| | |
| | 1)- SHEET A-3 WALL PRIORITY LEGAND: |
| | SBC 704.2.1.4. CORRIDOR PARTITIONS, |
| | SMOKESTOP PARTITIONS, HORIZONTAL EXIT |
| | PARTITIONS, EXIT ENCLOSURES AND FIRE |
| | RATED WALLS REQUIRED TO HAVE PROTECTED |
| | OPENINGS SHALL BE EFFECTIVELY & PERMAN- |
| | ETLY IDENTIFIED WITH SIGNS OR STENCILING |
| | : FIRE & SMOKE BARRIER PROTECT ALL OPEN- |
| | INGS. |
| | |
| | 2)- SHEET A-3 SBC 705.4.1 PROTECTION OF |
| | PENETRATIONS THROUGH FIRE RATED AND NON- |
| | FIRE RATED ASSEMBLIES SHALL COMPLY WITH |
| | 705.5(FIRE RATED WALLS) & 705.6 PENETRA- |
| | TIONS OF HORIZONTAL ASSEMBLIES (FLOORS, |
| | FLOOR/ CEILING ASSEMBLIES OR A ROOF |
| | CEILING ASSEMBLIES). REQUIRE A UL LIST- |
| | ING. |
| | |
| | 3)- SHEET F-0 IS MISSING THE MINIMUM |
| | INTERIOR FINISH CLASSIFICATION SBC |
| | TABLE 803.3. |
| | |
| | 4)- FL ACCESSIBILITY CODE 4.5. FLOOR |
| | SURFACES ALONG ACCESSIBLE ROUTES AND IN |
| | ACCESSIBLE ROOMS, SPACES INCLUDING RAMPS |
| | AND STAIRS SHALL BE STABLE, FIRM AND |
| | SLIP RESISTANT. ADDAAG A-5 A STATIC |
| | COEFFICIENT OF FRICTION OF 0.6 FOR |
| | ACCESSIBLE ROUTES & 0.8 FOR RAMPS. |
| | |
| | 5)- TYPE I TYPE II BUILDINGS REQUIRE |
| | FIRE SPRINKLER PLANS AS PART OF THE |
| | BUILDING PERMITED PLANS. (2 COPIES). |
| | FIRE SPRINKLER PERMIT WILL REQUIRE A |
| | SEPERATE PERMIT, PLANS WITH ASSOCIATED |
| | FEES. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561) 659-8096 X8412 |