| Plan Review Notes For Permit 01110421 |
| Permit Number |
01110421 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-02-07 00:00:00 | MECHANICAL PERMIT 02020462 | | | | | | PROVISO: | | | | | | EXHAUST DUCT SHALL HAVE A FIRE DAMPER | | | UNLESS IT MEETS ALL THE REQUIREMENTS OF | | | 1997 SMC 610.1.3 #3 - 1 THRU 4. | | | | | | 1.DUCT SHALL NOT EXCEED 100 SQ INCHES | | | 2.THE DUCT SHALL BE OF 0.0217 MINIMUM | | | STEEL | | | 3.THE DUCT SHALL CONTINUE WITH NO DUCT | | | OPENINGS FOR NOT LESS THAN 5 FT FROM | | | THE RATED WALL. | | | 4.THE DUCT SHALL BE INSTALLED ABOVE | | | THE CEILING. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|