2002-02-07 00:00:00MECHANICAL PERMIT 02020462
  
 PROVISO:
  
 EXHAUST DUCT SHALL HAVE A FIRE DAMPER
 UNLESS IT MEETS ALL THE REQUIREMENTS OF
 1997 SMC 610.1.3 #3 - 1 THRU 4.
  
 1.DUCT SHALL NOT EXCEED 100 SQ INCHES
 2.THE DUCT SHALL BE OF 0.0217 MINIMUM
 STEEL
 3.THE DUCT SHALL CONTINUE WITH NO DUCT
 OPENINGS FOR NOT LESS THAN 5 FT FROM
 THE RATED WALL.
 4.THE DUCT SHALL BE INSTALLED ABOVE
 THE CEILING.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.