2001-11-29 00:00:00*******************PROVISO**************
  
  
 PLAN SHEET M2.1, NOTE INDICATES 6"
 EXHAUST DUCT PENETRATING 1 HOUR FIRE
 RATED WALL A FIRE DAMPER IS NOT
 REQUIRED.
  
 AS PER 1997 SMC 510.1.2 #1, DUCTS
 PENETRATING WALLS OR PARTITIONS HAVING
 A FIRE RESISTANCE RATING OF 1 OR MORE
 HOURS.
  
 PLEASE CORRECT PLANS TO REFLECT FIRE
 DAMPERS.ALSO, O.A. DUCT INDICATES A
 DAMPER BUT DOES NOT SPECIFY A FIRE
 DAMPER OR A FIRE/SMOKE DAMPER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096.
 EXT. 8388.