| Plan Review Notes For Permit 01110421 |
| Permit Number |
01110421 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-11-29 00:00:00 | *******************PROVISO************** | | | | | | | | | PLAN SHEET M2.1, NOTE INDICATES 6" | | | EXHAUST DUCT PENETRATING 1 HOUR FIRE | | | RATED WALL A FIRE DAMPER IS NOT | | | REQUIRED. | | | | | | AS PER 1997 SMC 510.1.2 #1, DUCTS | | | PENETRATING WALLS OR PARTITIONS HAVING | | | A FIRE RESISTANCE RATING OF 1 OR MORE | | | HOURS. | | | | | | PLEASE CORRECT PLANS TO REFLECT FIRE | | | DAMPERS.ALSO, O.A. DUCT INDICATES A | | | DAMPER BUT DOES NOT SPECIFY A FIRE | | | DAMPER OR A FIRE/SMOKE DAMPER. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096. | | | EXT. 8388. |
|