Plan Review Notes
Plan Review Notes For Permit 01110412
Permit Number 01110412
Review Stop P
Sequence Number 6
Notes
Date Text
2002-07-22 00:00:00REVISION DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SANITARY RISERS A1, A2, B1, & B2.
 NO KITCHEN SINK OR WASH MACHINE TRAP
 SHALL BE PLACED ON A 2" COMBINED WASTE
 AND VENT. 3" WASTE AND VENT REQD.
 SECT. 911.4-SHT P5.31
  
 2) NO VENT THRU ROOF SHOWN ON ANY STACK.
 PLEASE INDICATE WHICH STACK/STACKS WILL
 VENT THRU ROOF. SHT P5.31
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377