| 2002-05-09 00:00:00 | ****************** UNSAT ************* |
| | |
| | 1)NOTE: PLEASE NOTE THAT E-SHEETS DO |
| | NOT HAVE AN ORIGINAL SIGNATURE FROM |
| | THE ARCH/ENGINEER OF RECORD. PLEASE |
| | NOTE THAT PER FS/FAC MUST BE AN ORIG |
| | SIGNATURE. 471.025/481.221. |
| | |
| | 2)NOTE: PLEASE NOTE, OUTLET SPACING FOR |
| | BALCONY/LOFT UNITS, STILL DO NOT MEET |
| | 210-52. PLEASE NOTE RAIL AREAS ARE STILL |
| | CONSIDERED 'WALL SPACE'. 210-52 ALSO |
| | INCLUDES COUNTERSPACE IN KITCHENS... |
| | PLEASE SEE 210-52C-1. |
| | PLEASE SEE 210-52A 1-2-3. |
| | |
| | |
| | |
| | |
| | 3)NOTE: PLEASE NOTE THAT PLANS KEEP |
| | GOING BACK AND FORTH FOR CONDUIT TYPE |
| | FOR FEEDERS TO UNITS. EMT IS PERMITTED |
| | ONLY IN EXPOSED ARES ABOVE GROUND. IF |
| | ANY OF THESE FEEDERS ARE IN THE SLAB OR |
| | POURED IN CONCRETE, DIRECT CONTACT WITH |
| | EARTH ETC. 348-5 |
| | PLEASE NOTE THAT PREVIOUS NOTE FOR THIS |
| | ITEM WAS THAT PLANS SHOWED "RIGID" |
| | CONDUIT AND ITS EXPENSE. PVC IS ALSO |
| | PEMITTED FOR SLABS. |
| | THIS WAS JUST A NOTE. |
| | |
| | 4)NOTE: PLEASE NOTE THAT PER FS/FAC |
| | PLANS DENIED FOR THE SAME COMMENTS MORE |
| | THAN 3 TIMES ARE SUBJECT TO 4X FEE FOR |
| | PLAN REVIEW PORTION OF TOTAL PERMIT FEE. |
| | PLAN REVIEW PORTION IS ABOUT 30% OF |
| | ORIG PERMIT FEE. PLEASE HAVE COMMENTS |
| | ADDRESSED. IF A MEETING IS NEEDED OR |
| | OVER THE PHONE? PLEASE NOTE, AS TO DATE |
| | NO ONE HAS CONTACTED ME FOR ANY QUESTION |
| | -S OR CLARIFICATIONS IF NEEDED. |
| | FS 553-80. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. ONCE AGAIN, IF THERE ARE ANY,,, |
| | QUESTIONS, PLEASE CALL.... |
| | |