Plan Review Notes
Plan Review Notes For Permit 01110412
Permit Number 01110412
Review Stop E
Sequence Number 4
Notes
Date Text
2002-05-09 00:00:00****************** UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT E-SHEETS DO
 NOT HAVE AN ORIGINAL SIGNATURE FROM
 THE ARCH/ENGINEER OF RECORD. PLEASE
 NOTE THAT PER FS/FAC MUST BE AN ORIG
 SIGNATURE. 471.025/481.221.
  
 2)NOTE: PLEASE NOTE, OUTLET SPACING FOR
 BALCONY/LOFT UNITS, STILL DO NOT MEET
 210-52. PLEASE NOTE RAIL AREAS ARE STILL
 CONSIDERED 'WALL SPACE'. 210-52 ALSO
 INCLUDES COUNTERSPACE IN KITCHENS...
 PLEASE SEE 210-52C-1.
 PLEASE SEE 210-52A 1-2-3.
  
  
  
  
 3)NOTE: PLEASE NOTE THAT PLANS KEEP
 GOING BACK AND FORTH FOR CONDUIT TYPE
 FOR FEEDERS TO UNITS. EMT IS PERMITTED
 ONLY IN EXPOSED ARES ABOVE GROUND. IF
 ANY OF THESE FEEDERS ARE IN THE SLAB OR
 POURED IN CONCRETE, DIRECT CONTACT WITH
 EARTH ETC. 348-5
 PLEASE NOTE THAT PREVIOUS NOTE FOR THIS
 ITEM WAS THAT PLANS SHOWED "RIGID"
 CONDUIT AND ITS EXPENSE. PVC IS ALSO
 PEMITTED FOR SLABS.
 THIS WAS JUST A NOTE.
  
 4)NOTE: PLEASE NOTE THAT PER FS/FAC
 PLANS DENIED FOR THE SAME COMMENTS MORE
 THAN 3 TIMES ARE SUBJECT TO 4X FEE FOR
 PLAN REVIEW PORTION OF TOTAL PERMIT FEE.
 PLAN REVIEW PORTION IS ABOUT 30% OF
 ORIG PERMIT FEE. PLEASE HAVE COMMENTS
 ADDRESSED. IF A MEETING IS NEEDED OR
 OVER THE PHONE? PLEASE NOTE, AS TO DATE
 NO ONE HAS CONTACTED ME FOR ANY QUESTION
 -S OR CLARIFICATIONS IF NEEDED.
 FS 553-80.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. ONCE AGAIN, IF THERE ARE ANY,,,
 QUESTIONS, PLEASE CALL....
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372