2002-05-08 00:00:00PLEASE NOTE SOME OF THE MECHANICAL
 PAGES HAVE A "STAMPED" SIGNATURE FOR THE
 ENGENEER INSTEAD OF A SIGNATURE. UNDER
 THE PROVISIONS OF CHAPTER 471 OF THE
 FLORIDA STATUES ALL PAGES SHALL HAVE AN
 ORIGINAL SIGNATURE NOT A STAMP.
  
 LETTER OF RESPONSE -
  
 MECHANICAL ITEM #1
  
 "CHASE IS A FIRE RATED SHAFT COMPLYING
 WITH SMC 610.4.SEE REVISED DRAWING
 A5.12."
  
 PLAN SHEET A5.12 IS NOT IN THE TYPE III
 SUBMITTAL.HOWEVER ON PLAN SHEET A5.32
 PLAN VIEW OF DRYER VENT DUCT THROUGH
 FLOORS TO ROOF.SEE PLAN SHEET A5.32
 FOR REVISED DRAWING (ATTACHED). PLEASE
 PROVIDE WHAT RATING (1 HR, 2 HR ?).
  
 SPECIFICATION FOR SPECIFIC DRYER ALSO
 SUBMITTED INDICATING ALLOWABLE LENGTH OF
 DUCT EXCEEDING THE CODE REQUIREMENT.
 PLEASE NOTE DRYERS SHALL BE INSTALLED
 FOR FINAL INSPECTION.
  
 DETAIL FOR THE RESTROOM EXHAUST VENTING
 ON PLAN SHEET M5.33, PLEASE NOTE SHOULD
 THE ALTERNATE DISCHARGE THROUGH THE ROOF
 BE USED IT SHALL COMPLY WITH 1997 SMC
 610.4. (DUCTS PENETRATING MORE THAN 1
 FLOOR SHALL BE PROTECTED BY A SHAFT
 ENCLOSURE).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.