| 2002-05-08 00:00:00 | PLEASE NOTE SOME OF THE MECHANICAL |
| | PAGES HAVE A "STAMPED" SIGNATURE FOR THE |
| | ENGENEER INSTEAD OF A SIGNATURE. UNDER |
| | THE PROVISIONS OF CHAPTER 471 OF THE |
| | FLORIDA STATUES ALL PAGES SHALL HAVE AN |
| | ORIGINAL SIGNATURE NOT A STAMP. |
| | |
| | LETTER OF RESPONSE - |
| | |
| | MECHANICAL ITEM #1 |
| | |
| | "CHASE IS A FIRE RATED SHAFT COMPLYING |
| | WITH SMC 610.4.SEE REVISED DRAWING |
| | A5.12." |
| | |
| | PLAN SHEET A5.12 IS NOT IN THE TYPE III |
| | SUBMITTAL.HOWEVER ON PLAN SHEET A5.32 |
| | PLAN VIEW OF DRYER VENT DUCT THROUGH |
| | FLOORS TO ROOF.SEE PLAN SHEET A5.32 |
| | FOR REVISED DRAWING (ATTACHED). PLEASE |
| | PROVIDE WHAT RATING (1 HR, 2 HR ?). |
| | |
| | SPECIFICATION FOR SPECIFIC DRYER ALSO |
| | SUBMITTED INDICATING ALLOWABLE LENGTH OF |
| | DUCT EXCEEDING THE CODE REQUIREMENT. |
| | PLEASE NOTE DRYERS SHALL BE INSTALLED |
| | FOR FINAL INSPECTION. |
| | |
| | DETAIL FOR THE RESTROOM EXHAUST VENTING |
| | ON PLAN SHEET M5.33, PLEASE NOTE SHOULD |
| | THE ALTERNATE DISCHARGE THROUGH THE ROOF |
| | BE USED IT SHALL COMPLY WITH 1997 SMC |
| | 610.4. (DUCTS PENETRATING MORE THAN 1 |
| | FLOOR SHALL BE PROTECTED BY A SHAFT |
| | ENCLOSURE). |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT 659-8096 |
| | EXT. 8388. |