Plan Review Notes
Plan Review Notes For Permit 01110412
Permit Number 01110412
Review Stop E
Sequence Number 3
Notes
Date Text
2002-03-18 00:00:00****************** UNSAT *************
  
 1)NOTE: PLEASE NOTE MISSING OUTLET
 SPACING TO MEET 210-52. 2' OF WALLS AND
 12' OF WALLS. ONE SET WAS REDLINED.
  
 2)NOTE: PLEASE NOTE MISSING LT REQ`D FOR
 MECH CLOSET.210-70
  
 3)NOTE: PLEASE NOTE THAT ON PREVIOUS
 REVIEW IT WAS NOTED THAT EMT COULD NOT
 BE USED FOR SERVICE ENTRANCE CONDUIT.
 PLEASE NOTE THAT NOW THE APT FEEDER
 CONDUITS WERE ALSO CHANGED. PLEASE NOTE
 THAT THESE MAY BE EMT. IF RIGID IS SHOWN
 ON PLANS THEN REGID WILL BE REQ`D TO BE
 INSTALLED. PLEASE VERIFY, THIS IS JUST
 NOTED DUE TO THE EXSPENSE OF RIGID BEING
 INSTALLED FOR APT SUB FEEDS.
  
 4)NOTE: PLEASE HAVE ALL OLD E-SHEETS
 REMOVED FROM SETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372