| Plan Review Notes For Permit 01110412 |
| Permit Number |
01110412 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-03-18 00:00:00 | ****************** UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE MISSING OUTLET | | | SPACING TO MEET 210-52. 2' OF WALLS AND | | | 12' OF WALLS. ONE SET WAS REDLINED. | | | | | | 2)NOTE: PLEASE NOTE MISSING LT REQ`D FOR | | | MECH CLOSET.210-70 | | | | | | 3)NOTE: PLEASE NOTE THAT ON PREVIOUS | | | REVIEW IT WAS NOTED THAT EMT COULD NOT | | | BE USED FOR SERVICE ENTRANCE CONDUIT. | | | PLEASE NOTE THAT NOW THE APT FEEDER | | | CONDUITS WERE ALSO CHANGED. PLEASE NOTE | | | THAT THESE MAY BE EMT. IF RIGID IS SHOWN | | | ON PLANS THEN REGID WILL BE REQ`D TO BE | | | INSTALLED. PLEASE VERIFY, THIS IS JUST | | | NOTED DUE TO THE EXSPENSE OF RIGID BEING | | | INSTALLED FOR APT SUB FEEDS. | | | | | | 4)NOTE: PLEASE HAVE ALL OLD E-SHEETS | | | REMOVED FROM SETS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|