2002-03-13 00:00:00 
 TYPE III
  
 DRYER EXHAUST FOR THE INTERIOR
 APARTMENTS - HVAC SHEET NOTES - #8 4"
 METAL DRYER EXHASUT VENT ROUTED UP IN
 CHASE & THROUGH THE ROOF.PLEASE
 PROVIDE DETAIL OF "CHASE".DUCTS
 EXTENDING THROUGH MORE THAN ONE FLOOR
 SHALL BE PROTECTED BY A SHAFT ENCLOSURE
 AS PER 1997 SMC 610.4.
  
 PLEASE NOTE, THE MAXIMUM LENGTH SHALL
 NOT EXCEED 25 FT FROMDRYER LOCATION
 TO WALL OR ROOF CAP.THERE SHALL BE A
 5 FT DEDUCTION FOR EACH 90 DEGREE BEND &
 2 1/2 FT FOR EACH 45 DEGREE BEND. THE
 WALL OR ROOF CAP SHALL BE NONSCREENED
 WITH A BACK DRAFT DAMPER. 1997 SMC 610.6
  
 BATHROOM EXHAUST - WALL CAP SHALL BE
 SCREENED.PLEASE INDICATE ACCESS FOR
 THE FIRE DAMPERS AS PER 1997 SMC 610.6.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.