Plan Review Notes
Plan Review Notes For Permit 01110412
Permit Number 01110412
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2002-02-12 00:00:001) CIVIL DRAWINGS ARE NEEDED FOR FIRE
 MAINS, FIRE HYDRANTS, ETC. WET FIRE
 HYDRANTS ARE REQUIRED PRIOR TO, DURING
 AND AFTER CONSTRUCTION.
 2) ARCHITECTURAL SITE MATRIX DOES NOT
 INDICATE ANY FIRE HYDRANT LOCATIONS.
 ALSO IT APPEARS THAT SECURITY ARMS
 OR GATES ARE BEING PROVIDED. WHAT
 PROVISIONS ARE MADE FOR FIRE RESCUE
 ACCESS. IF ELECTRIC, WHAT HAPPENS WHEN
 LOSS OF POWER OCCURS. ALL ROADS ARE TO
 BE A MINIMUM OF TWENTY FEET IN CLEAR
 WIDTH AND BE ABLE TO SUPPORT THE WEIGHT
 OF FIRE APPARATUS. WHAT IS THE
 DIFFERENCE BETWEEN PHASE ONE AND PHASE
 TWO.
 3) BUILDING ADDRESSES REQUIRED.
 4) PRESCRIPTIVE CODE REQUIREMENTS FOR
 ALL HANDRAILS AND GUARDRAILS SHOULD
 BE PROVIDED.
 5) PENETRATIONS SHOWN THRU RATED WALLS.
 DRYER VENTS INTO BREEZEWAYS.
 6) PLEASE INDICATE LOCATION OF THE
 FIRE ALARM CONTROL PANEL.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910