| Notes |
| Date |
Text |
| 2002-02-12 00:00:00 | 1) CIVIL DRAWINGS ARE NEEDED FOR FIRE | | | MAINS, FIRE HYDRANTS, ETC. WET FIRE | | | HYDRANTS ARE REQUIRED PRIOR TO, DURING | | | AND AFTER CONSTRUCTION. | | | 2) ARCHITECTURAL SITE MATRIX DOES NOT | | | INDICATE ANY FIRE HYDRANT LOCATIONS. | | | ALSO IT APPEARS THAT SECURITY ARMS | | | OR GATES ARE BEING PROVIDED. WHAT | | | PROVISIONS ARE MADE FOR FIRE RESCUE | | | ACCESS. IF ELECTRIC, WHAT HAPPENS WHEN | | | LOSS OF POWER OCCURS. ALL ROADS ARE TO | | | BE A MINIMUM OF TWENTY FEET IN CLEAR | | | WIDTH AND BE ABLE TO SUPPORT THE WEIGHT | | | OF FIRE APPARATUS. WHAT IS THE | | | DIFFERENCE BETWEEN PHASE ONE AND PHASE | | | TWO. | | | 3) BUILDING ADDRESSES REQUIRED. | | | 4) PRESCRIPTIVE CODE REQUIREMENTS FOR | | | ALL HANDRAILS AND GUARDRAILS SHOULD | | | BE PROVIDED. | | | 5) PENETRATIONS SHOWN THRU RATED WALLS. | | | DRYER VENTS INTO BREEZEWAYS. | | | 6) PLEASE INDICATE LOCATION OF THE | | | FIRE ALARM CONTROL PANEL. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|