| Plan Review Notes For Permit 01110412 |
| Permit Number |
01110412 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-02-05 00:00:00 | ***************** UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE THAT AN ELECTRICAL | | | RISER DIAGRAM IS NOW BEING SUBMITTED FOR | | | REVIEW. PLEASE NOTE THAT TYPE OF CONDUIT | | | IS SHOWN AS EMT? PLEASE NOTE THIS IS | | | NOT ALLOWED. | | | 2)NOTE: PLEASE NOTE SIZING OF OCP FOR | | | UNITS NEED TO BE NOTED. | | | | | | 3)NOTE: PLEASE CLARIFY ON PLANS WHERE | | | THE REQ`MENTS FOR FAIR HOUSING HEIGHTS | | | ARE? FHAR/CFR24 100.205 | | | | | | | | | | | | | | | 4)NOTE: PLEASE NOTE THAT THERE WERE | | | STILL SOMEOUTLETS MISSING PER 210-52 | | | UNIT-B ETC, WALLS AND BALCONIES. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | | | | 5)NOTE: SD`S REQD AT BOTTOM OF STAIRS. | | | \\NFPA-72 2-2.1.1.1. |
|