Plan Review Notes
Plan Review Notes For Permit 01110412
Permit Number 01110412
Review Stop E
Sequence Number 1
Notes
Date Text
2001-11-27 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 3) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
  
 4) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50.
 PLEASE SHOW THE GROUNDING ELECTRODE
 SYSTEM.
  
 5)NOTE: PLEASE PROVIDE A ONE-LINE DIA-
 GRAM SHOWING SERVICE. PLEASE SHOW THE
 LOACTION OF SERVICE.
  
 6)NOTE: PLEASE NOTE THAT ALL HOUSE
 CONTINUOUS LOADS ARE TO BE SHOWN AT 125%
  
 7)NOTE: PLEASE NOTE STORAGE ROOM TPYES
 OF FIXTURES AND CLEARENCES PER 410-8.
  
 8)NOTE: PLEASE SHOW EXIT LTS PER FIRE
 REVIEW COMMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE NAY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
  
  
 PLEASE NOTE THAT NOTES 22, PLEASE NOTE
 PER LOCAL AMENDMENTS,SE, NMC CABLES ETC
 ARE NOT PERMITTED.