| 2001-11-27 00:00:00 | **************** UNSAT **************** |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 2) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | |
| | 3) NOTE: PLEASE SHOW ALL OUTLET SPACING |
| | TO MEET 2`,6`,12` RULE PER 210-52. |
| | |
| | 4) NOTE: PLEASE SHOW GROUNDING ELECTRODE |
| | GOING TO BUILDING STEEL AND COLD WATER |
| | PER 250-50. |
| | PLEASE SHOW THE GROUNDING ELECTRODE |
| | SYSTEM. |
| | |
| | 5)NOTE: PLEASE PROVIDE A ONE-LINE DIA- |
| | GRAM SHOWING SERVICE. PLEASE SHOW THE |
| | LOACTION OF SERVICE. |
| | |
| | 6)NOTE: PLEASE NOTE THAT ALL HOUSE |
| | CONTINUOUS LOADS ARE TO BE SHOWN AT 125% |
| | |
| | 7)NOTE: PLEASE NOTE STORAGE ROOM TPYES |
| | OF FIXTURES AND CLEARENCES PER 410-8. |
| | |
| | 8)NOTE: PLEASE SHOW EXIT LTS PER FIRE |
| | REVIEW COMMENTS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE NAY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |
| | |
| | |
| | |
| | PLEASE NOTE THAT NOTES 22, PLEASE NOTE |
| | PER LOCAL AMENDMENTS,SE, NMC CABLES ETC |
| | ARE NOT PERMITTED. |