| Plan Review Notes For Permit 01110411 |
| Permit Number |
01110411 |
|
| Review Stop |
P |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2002-07-22 00:00:00 | REVISION DENIED | | | REFERENCE: SPC-94 - FACBC-97 | | | | | | 1) SANITARY RISERS A1, A2, B1, & B2 - | | | NO KITCHEN SINK OR WASHING MACHINE TRAP | | | SHALL BE PLACED ON A 2" COMBINED WASTE | | | AND VENT. 3" WASTE AND VENT STACK REQD. | | | SECT. 911.4-SHT P5.21 | | | | | | 2) NO VENT THRU ROOF SHOWN ON ANY STACK | | | PLEASE INDICATE WHICH STACK/STACKS WILL | | | VENT THRU ROOF. SHT P5.21 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|