Plan Review Notes
Plan Review Notes For Permit 01110411
Permit Number 01110411
Review Stop P
Sequence Number 6
Notes
Date Text
2002-07-22 00:00:00REVISION DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) SANITARY RISERS A1, A2, B1, & B2 -
 NO KITCHEN SINK OR WASHING MACHINE TRAP
 SHALL BE PLACED ON A 2" COMBINED WASTE
 AND VENT. 3" WASTE AND VENT STACK REQD.
 SECT. 911.4-SHT P5.21
  
 2) NO VENT THRU ROOF SHOWN ON ANY STACK
 PLEASE INDICATE WHICH STACK/STACKS WILL
 VENT THRU ROOF. SHT P5.21
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377