| 2002-05-10 00:00:00 | ******************* UNSAT ************* |
| | |
| | 1)NOTE: PLEASE NOTE THAT PLANS HAVE |
| | ORIGINAL WET SIGNATURE PER FS/FAC |
| | FOR ARCH/ ENGINEERS. 471.025/481.221 |
| | |
| | 2)NOTE: PLEASE NOTE PLANS STILL DO NOT |
| | MEET 210-52. PLEASE NOTE 210-52A 1,2,3 |
| | FOR WALL SPACE. 210-52C-1 FOR KITCHEN |
| | WALL SPACE. |
| | RAIL AREAS ARE CONSIDERED WALL SPACE. |
| | |
| | 3)NOTE: PLEASE NOTE THAT PER FS/FAC |
| | DESIGNE PROFESSIONALS ARE SUBJECT TO |
| | 4XFEE FOR PLANS HAVING THE SAME |
| | COMMENTS FOR MORETHAN 3 TIMES. |
| | 553-80 2BPORTION OF PLAN REVIEW FEE. |
| | |
| | 4)NOTE: PLEASE NOTE PLANS HAVE GONE BACK |
| | AND FORTH IN REF TO RIGID AND EMT |
| | BEING INSTALLED. PLEASE NOTE THAT PER |
| | LOCAL AMEDMENTS 348-5, ENT SHALL NOT |
| | BE USED POURED IN CONCRETE, SLAB/DIRECT |
| | CONTACT WITH EARTH ETC. PLEASE NOTE THAT |
| | PREVIOUS NOTE WAS JUST A NOTE. PLEASE |
| | NOTE THAT RIGID, PVC AND IMC MAY BE |
| | USED. PLEASE SEE LOCAL AMENDMENTS. |
| | |
| | PLEASE NOTE IF A MEETING IS REQ`D OR |
| | A CONFERENCE CALL TO OVER ANY QUESTIONS, |
| | OR TO CLARFIY ANYTHING, PLEASE CALL. |
| | AS TO DATE, NO ONE HAS CALLED TO CLARIFY |
| | ANYTHNG. |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN |
| | 561-659-8096 EXT 8372 |