| 2002-05-14 00:00:00 | PLEASE NOTE SOME OF THE MECHANICAL PAGES |
| | HAVE A "STAMPED" SIGNATURE FOR THE |
| | ENGINEER INSTEAD OF A SIGNATURE.UNDER |
| | THE PROVISIONS OF CHAPTER 471 OF THE |
| | FLORIDA STATUES, ALL PAGES SHALL HAVE |
| | AN ORIGINAL SIGNATURE NOT A STAMP. |
| | |
| | LETTER OF RESPONSE - MECHANICAL ITEM #1 |
| | |
| | "CHASE IS A FIRE RATED SHAFT COMPLYING |
| | WITH SMC 610.4.SEE REVISED DRAWING |
| | A512." |
| | |
| | PLAN SHEET A5.12 IS NOT IN THE TYPE II |
| | SUBMITTAL.HOWEVER ON PLAN SHEET A5.22 |
| | PLAN VIEW OF DRYER VENT DUCT THROUGH |
| | FLOORS TO ROOF.SEE PLAN SHEET A.522 |
| | FOR REVISED DRAWING (ATTACHED).PLEASE |
| | PROVIDE THE RATING OF THE "CHASE" (1HR, |
| | 2HR?). |
| | |
| | PLAN SHEET M5.23 NOTE #6 (DRYER VENT) |
| | REFERENCES A SBCC 610.1.3.3.NO SUCH |
| | CODE.PLEASE CORRECT. |
| | |
| | SPECIFICATION FOR SPECIFIC DRYER SALO |
| | SUBMITTED INDICATING ALLOWABLE LENGTH |
| | OF DUCT EXCEEDING THE CODE REUQIREMENT. |
| | PLEASE NOTE DRYERS SHALL BE INSTALLED |
| | FOR FINAL INPSPECTION. |
| | |
| | DETAIL FOR THE RESTROOM EXHASUT VENTING |
| | ON PLAN SHEET M5.33, PLEASE NOTE SHOULD |
| | THE ALTERNATE DISCHARGE THROUGH THE ROOF |
| | BE USED IT SHALL COMPLY WITH 1997 SMC |
| | 610.4 (DUCTS PENETRATING MORE THAN 1 |
| | FLOOR SHALL BE PROTECTED BY A SHAFT |
| | ENCLOSURE). |
| | |