| Plan Review Notes For Permit 01110411 |
| Permit Number |
01110411 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-03-18 00:00:00 | ******************** UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE THAT OUTLET SPACING | | | STILL NEEDS TO MEET 210-52. MISSING IN | | | BEDROOMS OF 2' OF WALL. MISSING ON | | | LOFT/BALCONY AREAS, 12' OF WALL SPACE. | | | | | | 2)NOTE: PLEASE NOTE THAT COMMENT WAS | | | MADE ON PREVIOUS COMMETS OF USING EMT | | | AS SERVICE ENTRANCE CONDUIT. IT HAS BEEN | | | NOTED THAT ALL FEEDER CONDUITS FROM | | | METER CENTER HAVE NOW BEEN CHANGED TO | | | RIGID ALONG WITH SEC`S. PLEASE NOTE THAT | | | IF PLANS SHOW RIGID FOR FEEDER, THEN | | | RIGID WILL BE REQ`D TO BE INSTALLED. | | | THIS IS JUST A NOTE TO VERFIY EXSPENSE? | | | | | | 3)NOTE: PLEASE HAVE ALL OLD E-SHEETS | | | REMOVED FROM PLANS BEFORE RESUBMITTING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | | | | | | | 4)NOTE: PLEASE NOTE UPSTAIRS MECH ROOM | | | AND MISSING LT REQ`D PER 210-70. |
|