| Plan Review Notes For Permit 01110411 |
| Permit Number |
01110411 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-03-13 00:00:00 | | | | TYPE II | | | | | | DRYER EXHAUST FOR THE INTERIOR | | | APARTMENTS - HVAC SHEET NOTES - #8 4" | | | METAL DRYER EXHAUST VENT ROUTED UP IN | | | CHASE & THROUGH TH ROOF.PLEASE | | | PROVIDE DETAIL OF "CHASE". DUCTS | | | EXTENDING THROUGH MORE THAN ONE FLOOR | | | SHALL BE PROTECTED BY A SHAFT ENCLOSURE | | | AS PER 1997 SMC 610.4. | | | | | | PLEASE NOTE, THE MAXIMUM LENGTH SHALL | | | NOT EXCEED 25 FT FROM DRYER LOCATION TO | | | WALL OR ROOF CAP. THERE SHALL BE A 5 FT | | | DEDUCTIONS FOR EACH 90 DEGREE BEND & 2 | | | 1/2 FT FOR A 45 DEGREE BEND.THE WALL | | | OR ROOF CAP SHALL BE NONSCREENED WITH | | | BACK DRAFT DAMPER. 1997 SMC 509.3. | | | | | | BATHROOM EXHAUST - WALL CAP SHALL BE | | | SCREENED.PLEASE INDICATE ACCESS FOR | | | THE FIRE DAMPERS AS PER 1997 SMC 610.6. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|