Plan Review Notes
Plan Review Notes For Permit 01110411
Permit Number 01110411
Review Stop M
Sequence Number 2
Notes
Date Text
2002-03-13 00:00:00 
 TYPE II
  
 DRYER EXHAUST FOR THE INTERIOR
 APARTMENTS - HVAC SHEET NOTES - #8 4"
 METAL DRYER EXHAUST VENT ROUTED UP IN
 CHASE & THROUGH TH ROOF.PLEASE
 PROVIDE DETAIL OF "CHASE". DUCTS
 EXTENDING THROUGH MORE THAN ONE FLOOR
 SHALL BE PROTECTED BY A SHAFT ENCLOSURE
 AS PER 1997 SMC 610.4.
  
 PLEASE NOTE, THE MAXIMUM LENGTH SHALL
 NOT EXCEED 25 FT FROM DRYER LOCATION TO
 WALL OR ROOF CAP. THERE SHALL BE A 5 FT
 DEDUCTIONS FOR EACH 90 DEGREE BEND & 2
 1/2 FT FOR A 45 DEGREE BEND.THE WALL
 OR ROOF CAP SHALL BE NONSCREENED WITH
 BACK DRAFT DAMPER. 1997 SMC 509.3.
  
 BATHROOM EXHAUST - WALL CAP SHALL BE
 SCREENED.PLEASE INDICATE ACCESS FOR
 THE FIRE DAMPERS AS PER 1997 SMC 610.6.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.