Plan Review Notes
Plan Review Notes For Permit 01110411
Permit Number 01110411
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2002-02-12 00:00:001) CIVIL DRAWINGS ARE NEEDED FOR FIRE
 MAINS AND FIRE HYDRANTS. WET FIRE
 HYDRANTS ARE REQUIRED PRIOR TO, DURING
 AND AFTER CONSTRUCTION.
 2) ARCHITECTURAL SITE MATRIX DOES NOT
 INDICATE ANY FIRE HYDRANT LOCATIONS.
 ALSO IT APPEARS THAT SECURITY ARMS OR
 GATES ARE BEING PROVIDED. WHAT
 PROVISIONS ARE MADE FOR FIRE RESCUE
 ACCESS. IF ELECTRIC, WHAT HAPPENS WHEN
 LOSS OF POWER OCCURS. ALL ROADS ARE
 TO BE A MINIMUM OF TWENTY FEET IN
 CLEAR WIDTH AND BE ABLE TO SUPPORT FIRE
 APPARATUS. WHAT IS THE DIFFERENCE
 BETWEEN PHASE ONE AND PHASE TWO.
 3) BUIDLING ADDRESSES REQUIRED.
 4) DOORS APPEAR TO OPPOSE EACH OTHER
 NEAR THE GARAGE.
 5) PLEASE PROVIDE PRESCRIPTIVE CODE
 REQUIREMENTS FOR ALL HANDRAILS AND
 GAURDRAILS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910