| Plan Review Notes For Permit 01110411 |
| Permit Number |
01110411 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-02-12 00:00:00 | 1) CIVIL DRAWINGS ARE NEEDED FOR FIRE | | | MAINS AND FIRE HYDRANTS. WET FIRE | | | HYDRANTS ARE REQUIRED PRIOR TO, DURING | | | AND AFTER CONSTRUCTION. | | | 2) ARCHITECTURAL SITE MATRIX DOES NOT | | | INDICATE ANY FIRE HYDRANT LOCATIONS. | | | ALSO IT APPEARS THAT SECURITY ARMS OR | | | GATES ARE BEING PROVIDED. WHAT | | | PROVISIONS ARE MADE FOR FIRE RESCUE | | | ACCESS. IF ELECTRIC, WHAT HAPPENS WHEN | | | LOSS OF POWER OCCURS. ALL ROADS ARE | | | TO BE A MINIMUM OF TWENTY FEET IN | | | CLEAR WIDTH AND BE ABLE TO SUPPORT FIRE | | | APPARATUS. WHAT IS THE DIFFERENCE | | | BETWEEN PHASE ONE AND PHASE TWO. | | | 3) BUIDLING ADDRESSES REQUIRED. | | | 4) DOORS APPEAR TO OPPOSE EACH OTHER | | | NEAR THE GARAGE. | | | 5) PLEASE PROVIDE PRESCRIPTIVE CODE | | | REQUIREMENTS FOR ALL HANDRAILS AND | | | GAURDRAILS. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|