| Plan Review Notes For Permit 01110411 |
| Permit Number |
01110411 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-02-06 00:00:00 | ******************* UNSAT ************ | | | | | | 1)NOTE: PLEASE NOTE OUTLET SPACING TO | | | MEET 210-52. PLEASE NOTE LOCATION STILL | | | MISSING. BALCONY/BEDROOM ENTRANCE WALLS | | | | | | 2)NOTE: PLEASE NOTE THAT NOW A RISER | | | DIAGRAM IS SUBMITTED FOR REVIEW, PLEASE | | | NOTE THAT SERVICE ENTRANCE CONDUIT IS | | | SHOWN AS EMT? THIS IS NOT PERMITTED. | | | | | | 3)NOTE: PLEASE CLARIFY WHERE THE FHAR | | | ARE SHOWN ON THE PLANS.24 CFR 100.205 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | | | | 4)NOTE: PLEASE NOTE SD`S REQ`D AT BOTTOM | | | OF STAIRS. NFPA-72 2-2.1.1.1 | | | | | | | | | 5)NOTE: PLEASE NOTE THAT OCP NEEDS TO | | | BE SHOWN FOR EACH UNIT. CAN BE TYPICAL. |
|