Plan Review Notes
Plan Review Notes For Permit 01110411
Permit Number 01110411
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-11-26 00:00:001) IT DEPENDS WHEN THE BUILDING IS
 OFFICIALLY SUBMITTED FOR PERMITS AS
 TO WHAT FIRE CODE THE BUILDING WILL
 BE REVIEWED UNDER. JANUARY 1, 2002, THE
 FIRE PREVENTION CODE WILL BE APPLICABLE
 WHICH INVOKES THE 2000 LIFE SAFETY CODE.
 2) BUILDING ADDRESS REQUIRED.
 3) SITE PLAN FOR FIRE PROTECTION
 DRAWINGS DOES NOT INDICATE STREET NAMES.
 4) NO HYDRAULIC CALCULATIONS PROVIDED
 WITH SPRINKLER PLANS.
 5) ILLUMINATED EXIT SIGNS NOT SHOWN ON
 ELECTRICAL DRAWINGS, FLOOR PLANS.
 6) FIRE DEPARTMENT CONNECTIONS TO BE
 LOCATED NE FARTHER THAN 150 FEET TO
 FIRE HYDRANTS.
 7) THE CITY OF RALEIGH NOTED ON PAGE
 F1.11.
 8) TRAVEL DISTANCE UNDER THE 1985
 EDITION OF THE LIFE SAFETY CODE ALLOWS
 ONLY 150 FEET IN SPRINKLERED APARTMENT
 BUILDINGS.
 9) PLEASE EXPLAIN USE OF LOFTS.
 10) GARAGE DOORS SHOWN ON PAGE A2.11
 APPEAR TO INTERSECT WITH ONE ANOTHER.
 11) WHAT FIRE RATING IS PRESENT FOR THE
 ALCOVES FROM THE GARAGE AND STORAGE
 AREAS.
 12) IS THERE ANY FIRE SEPARATION FOR
 THE STORAGE ROOMS.
 13) PLEASE INDICATE HEADROOM CLEARANCES
 FOR THE MEANS OF EGRESS AREAS.
 14) NO DIAGONAL DISTANCES SHOWN ON
 LS1.21.
 15) DRYER EXHAUST VENTS APPEAR TO
 PENETRATE EXIT CORRIDORS AND ONE HOUR
 WALLS.
 16) NO RATINGS PRESENT ON DOOR SCHEDULE
 FOR GARAGE DOORS WHICH APPEAR TO BE
 PART OF EXIT ACCESS AND COMMUNICATES
 WITH EXIT.
 17) FIRE PROTECTION APPEARS TO RUN
 UNDERNEATH THE BUILDING LIKE TYPE 1.
 THIS ARRANGEMENT IS NOT PERMITTED.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910