| Plan Review Notes For Permit 01110411 |
| Permit Number |
01110411 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-11-28 00:00:00 | ***************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE MISSING EXITS LTS. | | | PER FIRE REVIEW. | | | | | | 2)NOTE: PLEASE CLARIFY FIXTURES/CLEAR- | | | -ENCES PER 410-8 FOR STORAGE ROOM LTS. | | | | | | 3)NOTE: PLEASE NOTE ALL CONTINUOUS LOADS | | | ARE TO BE SHOWN AT 125% FOR HOUSE | | | PANELS.215-2,-3, 230-42 | | | | | | 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 5) NOTE: SMOKE DETECTORS ARE REQUIRED | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | | ALSO ON EACH LEVEL OF A MULTI-LEVEL | | | DWELLING UNIT. ROOMS WITH BATHS AND OR | | | CLOSETS ARE CONSIDERED SLEEPING ROOMS. | | | PER NFPA-72 2-2.1.1.1. | | | | | | 6) NOTE: PLEASE SHOW GROUNDING ELECTRODE | | | GOING TO BUILDING STEEL AND COLD WATER | | | PER 250-50. | | | SIZE PER 250-66 | | | | | | 7) NOTE: PLEASE SHOW ALL OUTLET SPACING | | | TO MEET 2`,6`,12` RULE PER 210-52. | | | | | | 8)NOTE: PLEASE NOTE THAT PLANS NEED TO | | | SHOW THE REQ`MENTS FOR FHAR,24CFR | | | 100.205. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | | | | PLEASE NOTE THE PER LOCAL AMENDMENTS | | | SE,NMC ETC IN NOTES (22) MAYNOT | | | BE USED. |
|