Plan Review Notes
Plan Review Notes For Permit 01110411
Permit Number 01110411
Review Stop E
Sequence Number 1
Notes
Date Text
2001-11-28 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE MISSING EXITS LTS.
 PER FIRE REVIEW.
  
 2)NOTE: PLEASE CLARIFY FIXTURES/CLEAR-
 -ENCES PER 410-8 FOR STORAGE ROOM LTS.
  
 3)NOTE: PLEASE NOTE ALL CONTINUOUS LOADS
 ARE TO BE SHOWN AT 125% FOR HOUSE
 PANELS.215-2,-3, 230-42
  
 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 5) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 6) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50.
 SIZE PER 250-66
  
 7) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
  
 8)NOTE: PLEASE NOTE THAT PLANS NEED TO
 SHOW THE REQ`MENTS FOR FHAR,24CFR
 100.205.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
 PLEASE NOTE THE PER LOCAL AMENDMENTS
 SE,NMC ETC IN NOTES (22) MAYNOT
 BE USED.