| Notes |
| Date |
Text |
| 2002-07-22 00:00:00 | REVISION DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) SANITARY RISERS A1, A2, B1, & B2- | | | NO KITCHEN SINK OR WASHING MACHINE TRAP | | | SHALL BE PLACED ON A 2" COMBINED WASTE | | | AND VENT. 3" WASTE AND VENT STACK REQD. | | | SECT. 911.4-SHT P5.11 | | | | | | 2) NO VENT THRU ROOF SHOWN ON ANY STACK. | | | PLEASE INDICATE WICH STACK/STACKS WILL | | | VENT THRU ROOF.SHT P5.11 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|