 BUILDING PLAN REVIEW
 PERMIT: 01110409
 ADD:EPOCH/PORTOFINO/MASTER TYPE I
 CONT: EPOCH
 TEL: (561)683-1052
 ST BLD CD =1997 STANDARD BUILDING CODE
  
 *****PROVISO*****
  
 1) WEDGE-ALL ANCHOR DETAILS, SINCE THE
 LOADING IS NOT GIVEN FOR TENSION OR
 SHEAR LOAD APPLICATIONS HAS THE EDGE FAC
 TOR ( REDUCTION) BEEN FACORED INTO THE
 SPACING?
 A) DETAIL "D" S-D1.1 EXTERIOR CONDITION
 @ LOFT 2X6 WALL SITTING ON TOP OF A 5"
 CONCRETE WALL? NO INFORMATION IS GIVEN,
 CONTACT SIMPSON ENG. TO SEE IF A DOUBLE
 REDUCTION WOULD BE REQUIRED SINCE YOU
 WOULD BE 2 1/2" AWAY ON BOTH SIDES?
 B) DETAIL# 3 2X6 WALL AT EDGE OF SLAB,
 WHAT REDUCTION HAS BEEN TAKEN? HOW FAR
 AWAY FROM THE EDGE OF THE SLAB SHALL THE
 WEDGE ANCHOR BE LOCATED?
  
 ADDITIONAL INFORMATION SHALL BE OBTAINED
 TO CLARIFY THE CONDITIONS LISTED ABOVE.
  