Plan Review Notes
Plan Review Notes For Permit 01110409
Permit Number 01110409
Review Stop E
Sequence Number 4
Notes
Date Text
2002-05-09 00:00:00************* UNSAT *******************
  
 1)NOTE: PLEASE NOTE THAT E- SHEETS DO
 NOT HAVE ORIGINAL SIGNATURE FROM THE
 ARCH/ENGINEER OF RECORD WHICH IS REQ`D
 UNDER FS/FAC 471.025/481.221
 MUST BE AN ORIG SIGNATURE.
  
 2)NOTE: PLEASE NOTE THAT OUTLET SPACINGS
 STILL NEED TO MEET 210-52. PLEASE SEE
 210-52C-1AND 210-52A 123
 PLEASE ALSO NOTE THAT RAIL SPACE IS
 CONSIDERED TO BE WALL SPACE.
  
 3)NOTE: PLEASE NOTE THAT PLANS HAVE
 GONE BACK AND FORTH IN REF TO RIGID AND
 EMT. PLEASE NOTE THAT PER LOCAL AMEND.
 EMT SHALL NOT BE USED , IN DIRECT
 CONTACT WITH EARTH, POURED ETC . PLEASE
 NOTE IT WAS JUST A NOTE, RIGID MAY BE
 USED AND ALSO PVC, IMC. PLEASE SEE
 348-5 LOCAL AMENDMENTS.
  
 4)NOTE:PLEASE NOTE THAT PER FS/ FAC
 553-80, PLANS THAT ARE DENIED MORETHAN
 3 TIMES FOR THE SAME COMMENTS ARE
 SUBJECT TO 4X FEE FOR THE PORTION SET
 ASIDE FOR PLAN REVIEW OF THE TOTAL
 PERMIT FEE. (30%)
  
 PLEASE NOTE THAT IF A MEETING IS REQ`D
 OR A CONFERENCE CALL TO CLARIFY ANYTHING
 AS TO DATE, NO ONE HAS CONTACTED ME
 WITH ANY QUESTIONS.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372