Plan Review Notes
Plan Review Notes For Permit 01110409
Permit Number 01110409
Review Stop M
Sequence Number 3
Notes
Date Text
2002-05-14 00:00:00PLEASE NOTE SOME OF THE MECHANICAL
 PAGES HAVE A "STAMPED" SIGNATURE FOR THE
 ENGINEER INSTEAD OF A SIGNATURE.UNDER
 THE PROVISIONS OF CHAPTER 471 OF THE
 FLORIDA STATUES, ALL PAGES SHALL HAVE
 AN ORIGINAL SIGNATURE NOT A STAMP.
  
 BUILDING PERMIT 01110409
  
 PROVIDE RATING OF UL425 FOR THE DRYER
 CHASE (1 HR, 2 HR?).
  
 SPECIFICATION FOR SPECIFIC DRYER ALSO
 SUBMITTED INDICATING THE ALLOWABLE
 LENGTH OF DUCT EXCEEDING THE CODE
 REQUIREMENT.PLEASE NOTE DRYERS SHALL
 BE INSTALLED FOR FINAL INSPECTION.
  
 DETAIL FOR THE RESTROOM EXHAUST VENTING
 ON PLAN SHEET M5.33, PLEASE NOTE SHOULD
 THE ALTERNATE DISCHARGE THROUGH THE ROOF
 BE USED IT SHALL COMPLY WITH 1997 SMC
 610.4. (DUCTS PENETRATING MORE THAN 1
 FLOOR SHALL BE PROTECTED BY A SHAFT
 ENCLOSURE).
  