Plan Review Notes
Plan Review Notes For Permit 01110409
Permit Number 01110409
Review Stop E
Sequence Number 3
Notes
Date Text
2002-03-18 00:00:00********************* UNSAT ************
  
 1)NOTE: PLEASE NOTE MISSING LT REQ`D FOR
 MECH ROOM UPSTAIRS PER 210-70.
  
 2)NOTE: PLEASE NOTE OUTLET SPACING STILL
 NEEDS TO MEET 210-52. BALCONY/LOFT WALL.
 BEDROOM WALLS. 2' OF WALL.
  
 3)NOTE: PLEASE NOTE, IT IS NOTED THAT
 THE FEEDER CONDUITS TO APT UNITS WERE
 ALSO CHANGED TO "RIGID" CONDUIT. THE
 COMMENT FROM THE PREVIOS REVIEW WAS FOR
 SERVICE ENTRANCE CONDUIT ONLY COMING
 FROM FPL. PLEASE NOTE IF RIGID IS SHOWN
 THE IT WILL BE REQ`D TO BE INSTALLED.
 PLEASE VERIFY IF CHANGING APT FEEDER
 CONDUIT STILL STANDS. RIGID STANDS TO
 BE MUCH MORE OF AN EXSPENSE.
  
 4)NOTE: PLEASE REMOVE ALL OLD E-SHEETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372