| Plan Review Notes For Permit 01110409 |
| Permit Number |
01110409 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-03-18 00:00:00 | ********************* UNSAT ************ | | | | | | 1)NOTE: PLEASE NOTE MISSING LT REQ`D FOR | | | MECH ROOM UPSTAIRS PER 210-70. | | | | | | 2)NOTE: PLEASE NOTE OUTLET SPACING STILL | | | NEEDS TO MEET 210-52. BALCONY/LOFT WALL. | | | BEDROOM WALLS. 2' OF WALL. | | | | | | 3)NOTE: PLEASE NOTE, IT IS NOTED THAT | | | THE FEEDER CONDUITS TO APT UNITS WERE | | | ALSO CHANGED TO "RIGID" CONDUIT. THE | | | COMMENT FROM THE PREVIOS REVIEW WAS FOR | | | SERVICE ENTRANCE CONDUIT ONLY COMING | | | FROM FPL. PLEASE NOTE IF RIGID IS SHOWN | | | THE IT WILL BE REQ`D TO BE INSTALLED. | | | PLEASE VERIFY IF CHANGING APT FEEDER | | | CONDUIT STILL STANDS. RIGID STANDS TO | | | BE MUCH MORE OF AN EXSPENSE. | | | | | | 4)NOTE: PLEASE REMOVE ALL OLD E-SHEETS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|