Plan Review Notes
Plan Review Notes For Permit 01110409
Permit Number 01110409
Review Stop P
Sequence Number 2
Notes
Date Text
2002-02-08 00:00:00DENIED
 REFERENCE: SPC-94 - FHA AMEND-98 DESIGN
 MANUAL
  
 1) SHT A0.11 UNIT TYPE A, INDICATE SPEC-
 IFICATION A OR B FOR BATHROOM AS REQUES-
 TED IN PREVIOUS PLAN REVIEW.
 2) SHT A0.11 HAS SPECIFICATION B LAY OUT
 AND SPEC. A CALLED OUT. TYPICAL FOR RM
 #'S B201, A101, AND C101. PLEASE CLAIRFY
 3) SHT A0.11 CLEAR FLOOR SPACE NOT SHOWN
 ON KITCHEN FIXTURES AND/OR APPLIANCES AS
 REQUIRED IN FHA DESIGN MANUAL.
 4) SHT A0.11 SHOW CLEAR FLOOR SPACE FOR
 ALL LAVS WHICH SHALL BE CENTERED ON
 CLEAR FLOOR SPACE, AND SHOW CLEAR FLOOR
 SPACE PROPERLY AT ALL TUBS AND SHOWERS.
 SEE FHA DESIGN MANUAL FOR EXAMPLES.
 5) SHT A0.11 ALL DIMENSIONS FOR WATER
 CLOSETS NOT SHOWN. SEE B-307 AN C-110.
 SHOWN IS 15" TO CENTER FROM ONE SIDE BUT
 NO MEASUREMENT FROM OTHER SIDE. 33" MIN.
 REQUIRED.
 6) SHT 2.12 SHOW ALL CLEANOUTS ON RISER
 DIAGRAM,
 7) SHT P5.11 SANITARY RISER (B-2) STILL
 REDUCES FROM 3" TO 2" ON RISER. 3" SHALL
 RUN UNDIMINISHED FROM CONNECTION TO BLDG
 DRAIN TO CONNECTION TO STACK VENT.
 SPC SEC 714.2
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377