Plan Review Notes
Plan Review Notes For Permit 01110409
Permit Number 01110409
Review Stop M
Sequence Number 2
Notes
Date Text
2002-03-13 00:00:00 
  
 DRYER EXHAUST FOR THE INTERIOR
 APARTMENTS - HVAC SHEET NOTES - #84"
 METAL DRYER EXHAUST VENT ROUTED UP IN
 CHASE & THROUGH THE ROOF.PLEASE
 PROVIDE DETAIL OF "CHASE".DUCTS
 EXTENDINGTHROUGH MORE THAN ONE FLOOR
 SHALL BE PROTECTED BY A SHAFT ENCLOSURE
 AS PER 1997 SMC 610.4.
  
 PLEASE NOTE, THE MAXIMUM LENGTH SHALL
 NOT EXCEED 25 FT FROM DRYER LOCATION TO
 WALL OR ROOF CAP.THERE SHALL BE A 5
 FT DEDUCTION FOR EACH 90 DEGREE BEND &
 2 1/2 FT DEDUCTION FOR EACH 45 DEGREE
 BEND.THE WALL OR ROOF CAP SHALL BE
 NONSCREENED WITH BACK DRAFT DAMPER.
 1997 SMC 509.3
  
 BATHROOM EXHAUST - WALL CAP SHALL BE
 SCREENED.PLEASE INDICATE ACCESS FOR
 THE FIRE DAMPER AS PER 1997 SMC 610.6.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.