Plan Review Notes For Permit 01110409
Permit Number 01110409
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2002-02-12 00:00:001) CIVIL DRAWINGS ARE REQUIRED SO A
 REVIEW CAN OCCUR FOR FIRE MAIN, FIRE
 HYDRANTS, ETC. WET FIRE HYDRANTS ARE
 REQUIRED PRIOR TO,DURING AND AFTER
 CONSTRUCTION.
 2) DOORS INTERSECT WITH ONE ANOTHER
 ON THE FIRST FLOOR PLAN.
 3) ARCHITECTURAL MATRIX DOES NOT
 INDICATE ANY FIRE HYDRANT LOCATIONS.
 ALSO IT APPEARS THAT SECURITY ARMS
 OR GATES ARE BEING PROVIDED. WHAT
 PROVISIONS ARE MADE FOR FIRE RESCUE
 ACCESS. IF ELECTRIC, WHAT HAPPENS WHEN
 LOSS OF POWER OCCURS. ALL ROADS ARE TO
 BE A MINIMUM OF AT LEAST 20 FEET IN
 CLEAR WIDTH AND ABLE TO SUPPORT FIRE
 APPARATUS. WHAT IS THE DIFFERENCE
 BETWEEN PHASE ONE AND PHASE TWO.
 4) BUILDING ADDRESSES REQUIRED.
 5) PLEASE SEE PREVIOUS FIRE PLAN
 REVIEW NOTES.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910