| Plan Review Notes For Permit 01110409 |
| Permit Number |
01110409 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-02-06 00:00:00 | ***************** UNSAT ************ | | | | | | 1)NOTE: PLEASE NOTE MISSING OUTLETS PER | | | 210-52. BALCONY AND WALLS IN BEDROOMS. | | | | | | 2)NOTE: MISSING REQ`D SD`S AT BOTTOM OF | | | STAIRS. NFPA-72 2-2.1.1.1 | | | | | | 3)NOTE: PLEASE CLARIFY EMT AS TYPE OF | | | CONDUIT FOR SERVICE? EMT IS NOT ALLOWED. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVEIW | | | 561-659-8096 EXT 8372 | | | | | | 4)NOTE: PLEASE NOTE THAT OCP NEEDS TO | | | BE SHOWN FOR UNITS. CAN BE TYPICAL. |
|