2002-02-06 00:00:00***************** UNSAT ************
  
 1)NOTE: PLEASE NOTE MISSING OUTLETS PER
 210-52. BALCONY AND WALLS IN BEDROOMS.
  
 2)NOTE: MISSING REQ`D SD`S AT BOTTOM OF
 STAIRS. NFPA-72 2-2.1.1.1
  
 3)NOTE: PLEASE CLARIFY EMT AS TYPE OF
 CONDUIT FOR SERVICE? EMT IS NOT ALLOWED.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVEIW
 561-659-8096 EXT 8372
  
 4)NOTE: PLEASE NOTE THAT OCP NEEDS TO
 BE SHOWN FOR UNITS. CAN BE TYPICAL.