Plan Review Notes
Plan Review Notes For Permit 01110409
Permit Number 01110409
Review Stop B
Sequence Number 11
Notes
Date Text
2002-12-31 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 01110409 MODEL TYPE I
 01110411 MODEL TYPE II
 01110412 MODEL TYPE III
 ADD: 4400 N MILITARY TRAIL
 CONT: EPOCH PROPERTIES
 TEL: (561)683-1072
 SBC= 1997 STANDARD BUILDING CODE
  
 SUBMITTAL: STORM SHUTTERS
 DENIED
  
 1) PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 SBC 1606.1.4.
 2)1997 SBC SECTION 103.6,
 1606.1.4& 1707.4
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
 ATTACHED IS A COPY OF THE CITIES
 STANDARD FOR THE IMPLEMENTATION OF
 HURRICANE MISSLE IMPACT PROTECTION,
 IN REGARDS TO PROCEDURES (1 & 2). ALSO
 ATTACHED IS A COPY OF A SAMPLE SCHEDULE
 FOR INSTALATION.
 PLEASE INDICATE WHAT MODEL TYPE
 BUILDING I,II, OR III. ALSO INDICATE ON
 THE SCHEDULE WHAT FLOOR YOU ARE INDICAT-
 ING. THE CITY STATED THAT ALL WINDOWS ON
 THE 2ND & 3RD FLOOR ARE TO BE LARGE
 MISSLE TESTED, INDICATE ON THE SCHEDULE.
 THE CITY AGREED THAT THE SLIDING GLASS
 DOORS ON THE 2ND & 3RD FLOOR COULD BE
 SHUTTERED AS STATED IN YOUR LETTER DATED
 JULY 22,02 WITH ADDITIONAL HELP FROM
 A TEMP LABOR LETTER DATED AUG 15,02.
 THE USE OF STORM PANELS FOR FIRST FLOOR
 OK, AS STATED IN IMPACT STANDARD, WITH
 THE SCHEDULE FOR INSTALLATION!!!!
 PLEASE PROVIDE THE ADDITIONAL INFOR-
 MATION REQUESTED SO WE MAY EXPEDITE THIS
 MATTER, FOR FURTHER CLARIFICATION
 CONTACT:
 JIM WITMER
 (561) 659-8096 X8412
 BUILDING PLAN REVIEW