| 2002-12-31 00:00:00 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 01110409 MODEL TYPE I |
| | 01110411 MODEL TYPE II |
| | 01110412 MODEL TYPE III |
| | ADD: 4400 N MILITARY TRAIL |
| | CONT: EPOCH PROPERTIES |
| | TEL: (561)683-1072 |
| | SBC= 1997 STANDARD BUILDING CODE |
| | |
| | SUBMITTAL: STORM SHUTTERS |
| | DENIED |
| | |
| | 1) PROVIDE STORM PANEL INFORMATION WITH |
| | INSTALLATION SCHEDULE AND KEY PLAN WITH |
| | SPECIFIC ANCHORS AND MOUNTING TO BE USED |
| | FOR ALL NON-IMPACT GLAZING. |
| | SBC 1606.1.4. |
| | 2)1997 SBC SECTION 103.6, |
| | 1606.1.4& 1707.4 |
| | PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| | SCHEDULE SUMMARIZING & IDENTIFYING |
| | OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM |
| | BAR REINFORCING REQUIREMENTS, WALL PRES- |
| | SURE ZONES, SLAT TYPES, ETC., SHALL BE |
| | SUBMITTED AT TIME OF PERMIT APPLICATION |
| | TO FACILITATE PLAN REVIEW AND PERMIT |
| | ISSUANCE. |
| | ATTACHED IS A COPY OF THE CITIES |
| | STANDARD FOR THE IMPLEMENTATION OF |
| | HURRICANE MISSLE IMPACT PROTECTION, |
| | IN REGARDS TO PROCEDURES (1 & 2). ALSO |
| | ATTACHED IS A COPY OF A SAMPLE SCHEDULE |
| | FOR INSTALATION. |
| | PLEASE INDICATE WHAT MODEL TYPE |
| | BUILDING I,II, OR III. ALSO INDICATE ON |
| | THE SCHEDULE WHAT FLOOR YOU ARE INDICAT- |
| | ING. THE CITY STATED THAT ALL WINDOWS ON |
| | THE 2ND & 3RD FLOOR ARE TO BE LARGE |
| | MISSLE TESTED, INDICATE ON THE SCHEDULE. |
| | THE CITY AGREED THAT THE SLIDING GLASS |
| | DOORS ON THE 2ND & 3RD FLOOR COULD BE |
| | SHUTTERED AS STATED IN YOUR LETTER DATED |
| | JULY 22,02 WITH ADDITIONAL HELP FROM |
| | A TEMP LABOR LETTER DATED AUG 15,02. |
| | THE USE OF STORM PANELS FOR FIRST FLOOR |
| | OK, AS STATED IN IMPACT STANDARD, WITH |
| | THE SCHEDULE FOR INSTALLATION!!!! |
| | PLEASE PROVIDE THE ADDITIONAL INFOR- |
| | MATION REQUESTED SO WE MAY EXPEDITE THIS |
| | MATTER, FOR FURTHER CLARIFICATION |
| | CONTACT: |
| | JIM WITMER |
| | (561) 659-8096 X8412 |
| | BUILDING PLAN REVIEW |