Plan Review Notes
Plan Review Notes For Permit 01110409
Permit Number 01110409
Review Stop P
Sequence Number 1
Notes
Date Text
2001-11-30 00:00:00DENIED
 REFERENCE: SPC-94- FHA AMEND-98
 DESIGN MANUAL
  
 1) SHT A0.31 FAIR HOUSING PLANS. FHA-98
 DESIGN MANUAL, PLEASE COMPLY WITH REQ-
 UIREMENTS 1 THRU 7. REQ 7 PART B, PLEASE
 INDICATE SPECIFICATION A OR B FOR EACH
 FIRST FLOOR UNIT.
 2) SHT A0.31, PLEASE SHOW CLEAR FLOOR
 SPACE FOR ALL REQUIRED FIXTURES. (SEE
 PAGE 7.43)
 3) TYPICAL DOUBLE LAV - OFFSET BASIN AT
 DOUBLE LAVS, (SEE PAGE 7.48), FOR COUNT-
 ER AT LEAST 60" LONG. FOR SHORTER COUNT-
 ERS FORWARD APPROACH IS REQUIRED AND THE
 VANITY WILL HAVE TO BE REMOVABLE. (SEE
 PAGE 7.49) GIVE A DETAIL IN PLANS
 4) SHOW DEMENSIONS FOR ALL 1ST FLOOR W/C
 OPENINGS THAT HAVE NO DEMEMTIONS.
 5) SHT P2.31 2-WAY CLEAN OUTS ARE REQUI-
 RED AT EACH BREEZWAY. SPC SEC 710.2.4
 MAXIMUM 80' BETWEEN C/O'S.
 6) TYPICAL OF ALL UNITS, MAXIMUM 6' FOR
 2" TRAP FROM VENT. SPC TABLE 908.1. TUBS
 SCALE OUT TO BE FARTHER THAN ALLOWED.
 7) PROVIDE SANITARY RISER DIAGRAM FOR
 FIRST FLOOR HORIZONTAL BLDG DRAIN. SHOW
 ALL PIPE SIZES AND DRAINAGE FIXTURE
 UNITS EACH SECTION OF PIPE DRAINS. SHOW
 NUMBER OF FIXTURE UNITS DRAINING FROM
 EACH SANITARY RISER. (STACK)
 8) SHT P4.31 WATER HEATER DETAIL. DI-
 ELECTRIC UNIONS NOT APPROVED.
 9) SHT P4.31 DETAILS 6D & 7D WATER METER
 NOT APPROVED PER CITY CODE SEC 31-29
 SEE ATTACHED SHEET.
 10) SHT PR.31 WATER HEATER DETAIL. SAFE-
 TY PAN SHALL BE OF SUFFICIENT SIZE AND
 SHAPE TO RECIEVE ALL DRIPPINGS OR CON-
 DENSATE FROM TANK OR HEATER - DRAIN
 VALVE MUST BE INSIDE PAN. SEC 507.8.2
 11) SHT P4.31 ELECT. WATER HEATER SCHED.
 PER SPC TABLE 504 B-UNITS SHALL HAVE 40
 GAL W/HEATERS. C-UNITS SHALL HAVE 50 GAL
 W/HEATERS. ONLY 30 & 40 ARE SHOWN.
 12) SHT P5.31 SANITARY RISERS B1 & B2
 SHALL NOT REDUCE TO 2", BUT SHALL RUN
 UNDIMINISHED IN SIZE FROM ITS CONNECTION
 TO THE BLDG DRAIN TO ITS CONNECTION TO
 THE STACK VENT. SPC SEC 714.2
 13) AN APPROVED CIVIL DRAWING IS REQUIR-
 ED FOR FINAL APPROVAL OF PLUMBING PLANS.
 14) RPZ BACKFLOW REQUIRED FOR EACH BLDG.
 TYPE I, 2, & 3.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377