| Date |
Text |
| 2001-11-30 00:00:00 | DENIED |
| | REFERENCE: SPC-94- FHA AMEND-98 |
| | DESIGN MANUAL |
| | |
| | 1) SHT A0.31 FAIR HOUSING PLANS. FHA-98 |
| | DESIGN MANUAL, PLEASE COMPLY WITH REQ- |
| | UIREMENTS 1 THRU 7. REQ 7 PART B, PLEASE |
| | INDICATE SPECIFICATION A OR B FOR EACH |
| | FIRST FLOOR UNIT. |
| | 2) SHT A0.31, PLEASE SHOW CLEAR FLOOR |
| | SPACE FOR ALL REQUIRED FIXTURES. (SEE |
| | PAGE 7.43) |
| | 3) TYPICAL DOUBLE LAV - OFFSET BASIN AT |
| | DOUBLE LAVS, (SEE PAGE 7.48), FOR COUNT- |
| | ER AT LEAST 60" LONG. FOR SHORTER COUNT- |
| | ERS FORWARD APPROACH IS REQUIRED AND THE |
| | VANITY WILL HAVE TO BE REMOVABLE. (SEE |
| | PAGE 7.49) GIVE A DETAIL IN PLANS |
| | 4) SHOW DEMENSIONS FOR ALL 1ST FLOOR W/C |
| | OPENINGS THAT HAVE NO DEMEMTIONS. |
| | 5) SHT P2.31 2-WAY CLEAN OUTS ARE REQUI- |
| | RED AT EACH BREEZWAY. SPC SEC 710.2.4 |
| | MAXIMUM 80' BETWEEN C/O'S. |
| | 6) TYPICAL OF ALL UNITS, MAXIMUM 6' FOR |
| | 2" TRAP FROM VENT. SPC TABLE 908.1. TUBS |
| | SCALE OUT TO BE FARTHER THAN ALLOWED. |
| | 7) PROVIDE SANITARY RISER DIAGRAM FOR |
| | FIRST FLOOR HORIZONTAL BLDG DRAIN. SHOW |
| | ALL PIPE SIZES AND DRAINAGE FIXTURE |
| | UNITS EACH SECTION OF PIPE DRAINS. SHOW |
| | NUMBER OF FIXTURE UNITS DRAINING FROM |
| | EACH SANITARY RISER. (STACK) |
| | 8) SHT P4.31 WATER HEATER DETAIL. DI- |
| | ELECTRIC UNIONS NOT APPROVED. |
| | 9) SHT P4.31 DETAILS 6D & 7D WATER METER |
| | NOT APPROVED PER CITY CODE SEC 31-29 |
| | SEE ATTACHED SHEET. |
| | 10) SHT PR.31 WATER HEATER DETAIL. SAFE- |
| | TY PAN SHALL BE OF SUFFICIENT SIZE AND |
| | SHAPE TO RECIEVE ALL DRIPPINGS OR CON- |
| | DENSATE FROM TANK OR HEATER - DRAIN |
| | VALVE MUST BE INSIDE PAN. SEC 507.8.2 |
| | 11) SHT P4.31 ELECT. WATER HEATER SCHED. |
| | PER SPC TABLE 504 B-UNITS SHALL HAVE 40 |
| | GAL W/HEATERS. C-UNITS SHALL HAVE 50 GAL |
| | W/HEATERS. ONLY 30 & 40 ARE SHOWN. |
| | 12) SHT P5.31 SANITARY RISERS B1 & B2 |
| | SHALL NOT REDUCE TO 2", BUT SHALL RUN |
| | UNDIMINISHED IN SIZE FROM ITS CONNECTION |
| | TO THE BLDG DRAIN TO ITS CONNECTION TO |
| | THE STACK VENT. SPC SEC 714.2 |
| | 13) AN APPROVED CIVIL DRAWING IS REQUIR- |
| | ED FOR FINAL APPROVAL OF PLUMBING PLANS. |
| | 14) RPZ BACKFLOW REQUIRED FOR EACH BLDG. |
| | TYPE I, 2, & 3. |
| | |