| Plan Review Notes For Permit 01110409 |
| Permit Number |
01110409 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-02-07 00:00:00 | | | | | | | BUILDING TYPE I - PERMIT 01110409 | | | | | | AS PER 2000 LIFE SAFETY CODE CHAPTER 7 - | | | 7.1.3.1 EXIT ACCESS CORRIDORS | | | | | | (E) PENETRATIONS INTO AND OPENINGS | | | THROUGH AN EXIT ENCLOSURE ASSEMBLY | | | SHALL BE PROHIBITED EXCEPT FOR THE | | | FOLLOWING. | | | | | | (1) ELECTRICAL CONDUIT SERVING THE | | | STAIRWAY | | | (2) REQUIRED EXIT DOORS | | | (3) DUCTWORK & EQUIPMENT NECESSARY FOR | | | INDEPENDENT STAIR PRESSURIZATION | | | (4) WATER OR STEAM PIPING NECESSARY | | | FOR THE HEATING OR COOLING OF THE | | | EXIT ENCLOSURE | | | (5) SPRINKLER PIPING | | | (6) STANDPIPES | | | | | | ALSO AS PER 1997 SMC 610.1.2, FIRE | | | DAMPERS REQUIRED WHERE DUCTS PENETRATE | | | WALLS OR PARTITIONS HAVING A FIRE | | | RESISTANCE RATING OF 1 OR MORE HOURS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|