Plan Review Notes
Plan Review Notes For Permit 01110409
Permit Number 01110409
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-11-26 00:00:001) IT DEPENDS WHEN THE BUILDING IS
 OFFICIALLY SUBMITTED FOR PERMIT AS TO
 WHAT FIRE CODE THE BUILDING WILL BE
 REVIEWED UNDER. JANUARY 1, 2002, THE
 FIRE PREVENTION CODE WILL BE APPLICABLE
 WHICH INVOKES THE 2000 LIFE SAFETY CODE.
 2) BUILDING ADDRESS REQUIRED.
 3) SITE PLAN FOR FIRE PROTECTION
 DRAWINGS DOES NOT INDICATES STREET
 NAMES.
 4) NO HYDRAULIC CALCULATIONS PROVIDED
 WITH SPRINKLER PLANS.
 5) ILLUMINATED EXIT SIGNS NOT SHOWN
 ON ELECTRICAL DRAWINGS, FLOOR PLANS.
 6) FIRE DEPARTMENT CONNECTIONS TO BE
 LOCATED NO FARTHER 150 FEET TO FIRE
 HYDRANTS.
 7) THE CITY OF RALEIGH NOTED ON PAGE
 F1.11
 8) TRAVEL DISTANCE UNDER THE 1985
 EDITION OF THE LIFE SAFETY CODE ALLOWS
 ONLY 150 FEET IN SPRINKLERED APARTMENT
 BUILDINGS.
 9) PLEASE EXPLAIN USE OF LOFTS.
 10) THIRD FLOOR PLAN ON LS1.12, FIRE
 RATING APPEARS TO RUN IN MIDDLE OF
 CORRIDOR.
 11) GARAGE DOORS SHWON ON PAGE A2.11
 APPEAR TO INTERSECT WITH ONE ANOTHER.
 12) WHAT FIRE RATING IS PRESENT FOR THE
 ALCOVES FROM THE GARAGE AND STORAGE
 AREAS.
 13) IS THERE ANY FIRE SEPARATION FOR
 THE STORAGE ROOMS.
 14) PLEASE INDICATE HEADROOM CLEARANCES
 FOR THE MEANS OF EGRESS AREAS.
 15) WHAT ARE THE ROOMS ADJACENT TO THE
 STOREROOMS USED FOR.
 16) PLEASE VERIFY SEPARATION DISTANCES
 OF STAIRS. DIMENSIONS ON PAGE A2.11 DO
 NOT MEET DISTANCES ON PAGE LS1.11.
 17) FIRE SPRINKLER PROTECTION NOT SHOWN
 FOR UNITS A,B, AND C A3.11,A3.12,AND
 A3.13.
 18) DRYER EXHAUST VENTS APPEAR TO
 PENETRATE EXIT CORRIDORS AND ONE HOUR
 WALLS.
 19) GARAGE DOORS LABELED IN CORRECTLY
 ON PAGE A5.11.
 20) NO RATINGS PRESENT ON DOOR SCHEDULE
 FOR GARAGE DOORS WHICH APPEAR TO BE
 PART OF EXIT ACCESS AND COMMUNICATES
 WITH EXIT.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910