2001-12-14 00:00:00BUILDING PLAN REVIEW
 PLAN REVIEW # 01110409
 BRIGER TRACT "D"
 BUILDING TYPE I
  
 FLOOR AREA:
 1ST FL 15,569 SQ FT
 2ND FL 15,470 SQ FT
 3RD FL9,813 SQ FT
 LOFT 3,834 SQ FT
 TOTAL44,686 SQ FT
  
 NO SITE SURVEY / PLOT PLAN TO BE ABLE TO
 CHECK TABLE 600 ISSUES, HORIZONTAL
 SEPERATION, NOR ADDRESSING. WHAT IS
 FILED UNDER FIRE IS UNREADABLE AS TO
 WHAT TYPE OF BUILDINGS OR SITE FEATURES.
  
 WILL SITE ADDRESSING TAKE A WINDSOR WAY
 ADDRESS? OR WILL THERE BE A PRIVATE
 STREET NAME BE SUBMITTED? WILL TRACT"D"
 AND TRACT "C" HAVE THE SAME DEVELOPMENT
 NAME? SINCE THE PROPERTIES ARE ON (2)
 SEPERATE PROPERTIES THEY WILL REQUIRE
 2 ADDRESSES OR WILL THERE BE A UNITY OF
 TITLE?
  
 1006.2.1 EXTERIOR STAIRS: THE STAIRWAYS
 DEPCTED DO NOT COMPLY WITH THE DEFINI-
 TION OF EXTERIOR STAIRS. BREEZEWAY: A
 COVERED PASSAGEWAY AS BETWEEN A HOUSE/
 GARAGE, OFTEN ENCLOSED ON BOTH SIDES, W/
 OPEN ENDS AND A ROOF.
 BALCONY: A PLATFORM PROJECTING FROM THE
 BUILDING WITH A RAILING.
 PORCH: A COVERED ENTRANCE
 A SAMPLE PAGE OF OPEN EXTERIOR STAIRS
 FROM THE CODE COMMENTARY IS ATTACHED.
 SBC 1006.2.2 THE STAIR ARANGEMENTS DO
 NOT MEET THE CRITERIA OF THIS SECTION,
 THEY DO NOT MEET THE 1/2 THE DIAGONAL,
 PLUS MEETING THE 10' OPENING PROTECTIVES
 REQUIRED IN SBC 1006.2.4.OPENING WITHIN
 THE 10' HORIZONTALLY FROM EACH SIDE OF
 THE STAIRWAY SHALL BE EQUIPPED WITH FIX-
 ED 3/4 HR ASSEMBLIES.
 SBC TABLE 1007.1 CODE COMMENTARY INDICAT
 ES FOR TYPE V BUILDINGS RESIDENTIAL USE
 STAIRS 3 STORIES & GREATER REQUIRE NON-
 COMBUSTIBLE MATERIAL, SHOW COMPLIANCE
 WITH WOOD TRUSS FLOOR SYSTEM, STRUCTURAL
 DRAWINGS DO NOT INDICATE THE INTERMEDI-
 ATE FLOOR LANDINGS.
 IF STAIR & BREEZEWAY WERE ACCEPTED, THE
 1 HR SEPERATION SHALL BE MAINTAINED,
 M2.1 /M2.32 INDICATE THE BATH EXHAUST
 THRU TO BREEZEWAY.1006.2.4.
  
 SHEET A.3.31-A3.34 ILLEGAL WINDER SEE
 SECTION 1007.8.1.
  
 SHEET A3.34/F2.12 TYPE V FULLY SPRINKLER
 ED BUILDING. PLANS DO NOT SHOW FIRE
 SPRINKLERS IN GARAGE OR BREEZEWAY INTERM
 EDIATE LANDINGS OR ROOF TRUSSES.
 CS1.01 CODE SUMMARY(E) CONSTRUCTION TYPE
 RESIDENTIAL FULLY SPRINKLERED.PLANS
 INDICATE NFPA(13R) THIS SYSTEM WILL NOT
 ALLOW FOR THE HEIGTH MODIFICATION IN
 TABLE 500,FOOTNOTE "H".903.2 REQUIREMENT
 CITY OF RALIEGH, PLEASE CORRECT.
  
 SHEET M2.31/ M2.32 NOTE#5 INDICATES A
 RATED CHASE FOR REFRIGARANT LINES & CON-
 DENSATE LINES? SEC 705.2.2 SHAFT ENCLOS-
 URES, GIVE UL OR GYPSUM ASSEMBLY NUMBER.
  
 MEZZANINE SECTION 503.2.3:
 TYPE I BUILD : OK
 TYPE II BUILD:
 BALCONY SQ FT OVER
 SOLARIUM SQ FT OVER
 TYPE III BUILD:
 BALCONY SQ FT OVER
 SOLARIUM SQ FT OVER
  
 SHEET A-5.33 DRAFTSTOPPING REQ. 2305.2.2
 (2) FL/CEIL ASSEMBLY GARAGE / 2ND FL.
 A3.3.4 BLOCK DOES NOT EXTEND ABOVE THE
 FLOOR TRUSSES AT ENTRY HALL? STOREROOMS?
  
 SHEET S1.11 FASTENING SUBSTITUTION FAST-
 ENING SCHEDULE: STATES THAT THE NAILING
 FASTENERS PATERNS FOR SUBSTITUTE FASTEN-
 ERS SHALL USE THE SAME SCHEDULE CONVER-
 SION CHART FOR "ALLOWABLE LOADS ADJUST-
 MENT FACTORS" NOT THE SAME TENSION LOADS
 SEE MANUFACTURES LOAD CHARTS.
  
 SHEET S3.13 DETAIL #12 INDICATES USE OF
 COLUMN TO WOOD POST, WHERE IS THIS TO BE
 USED?
  
 ROOF SHEATHING SCHEDULE SBC TABLE 2306.1
 (COUNTY AMENDMENTS) ARE GOOD TO A HEIGTH
 OF 35'. ENGINEER SHALL INDICATE NAILING
 SCHEDULE FOR ABOVE 35'.
  
 SHEET S2.35 ROOF FRAMING PLAN INDICATE
 THE MAGNITUDE OF LOADS TO BE RESISTED,
 VERTICAL, HORIZONTAL & GRAVITY AND THE
 TYPE OF FASTENER REQUIRED FOR EACH AREA.
  
 SBC 1606.2.6.2 COMPONENTS & CLADDING
 DOOR & WINDOW BUCK ATTACHMENTS : NOT
 FOUND IN STRUCTURAL SHEETS.
 GLAZED OPENINGS REQUIRE LARGE MISSLE
 IMPACT RESISTANCE TESTING: SEE CITY
 POLICY AS TO REQUIREMENTS FOR LARGE
 COMPLEXES, COPY ATTACHED. (3 COPIES
 OF PRODUCT APPROVAL SHALL BE REQUIRED
 FOR EACH TYPE OF OPENING)
 ROOFING : ROOFING ASSEMBLIES SHALL ALSO
 REQURIE PRODUCT TESTING REPORTS FOR
 WIND ZONE 110.
 MULLIONS SHALL REQUIRE PRODUCT TESTING
 IF GLAZED UNIT WASN'T TESTED W/ MULLION
 DADE COUNTY OR SBCCI REPORTS ARE
 ACCEPTED.
  
 THIS PROJECT SHALL QUALIFY FOR A
 RESIDENT INSPECTOR. THE INSPETOR SHALL
 MEET WITH ASSISTANT BUILD DON NEELY
 TO REGISTER BEFOR ISSUANCE OF PERMIT.
  
 COUNTY IMPACT FEES SHALL BE PAID BY THE
 CONTRACTOR, CONTRACTOR SHALL SUBMIT
 PLANS TO THE COUNTY FOR IMPACT FEE
 ASSESSMENT.
  
 AT TIME OF ISSUANCE CONTRACTOR WILL PAY
 RADON FEES.
  
 PLANS ARE TO STATE CLEARLY ON ELEVATIONS
 THE APPROPRIATE WIND PRESSURES FOR
 DOORS AND WINDOWS,INCLUDING END ZONES.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X8412