2002-03-26 00:00:00BUILDING PLAN REVIEW
 PLAN REVIEW # 01110408
 SITE AMENITIES
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS STANDARD BUILDING CODE
  
 BATH HOUSE & REMOTE GARAGE PLAN
  
 1)- SBC 1606.2.6.2 COMPONENTS & CLADDING
 3 COPIES OF ALL PRODUCT ACCEPTANCE TEST-
 ING REPORTS SHALL BE REQUIRED FOR: ALL
 GLAZED OPENINGS, EXT. DOORS, SKYLIGHTS,
 GLASS BLOCK,STORM SHUTTERS AS WELL AS
 ROOFING ASSEMBLIES.WHEN REPORTS ARE NOT
 FILED, PLANS ARE APPROVED, WITH THE
 STIPULATION THAT A SEPERATE PERMIT WITH
 ASSOCIATED FEES SHALL BE REQUIRED, ALSO
 THE CITIES GUIDELINES FOR LARGE PROJECTS
 REGARDING PROTECTION FOR ALL GLAZED OPEN
 INGS SHALL BE ADHERRED TO, SEE ATTACHED
 GUIDELINES. THE BUILDING OFFICIAL SHALL
 REVIEW AND APPROVE ALL PROPOSED PRE-
 STORM PREPERATION PLAN.
  
 2)- THE TRUSS & GIRDER LAYOUT DOES NOT
 INDICATE THE UPLIFT LOADS TO BE RESISTED
 THERE IS A ANCHOR SCHEDULE INDICATING
 WHAT TYPE OF ANCHORS ARE TO BE USED.
 WITH OUT THIS INFORMATION BEOFRE THE
 ISSUANCE OF A BUILDING PERMIT THE ARCH
 AND ENGINEER SHALL BE REQUIRED TO
 REVIEW THE TRUSS PLAN LAYOUT AND ENGINEE
 RING CERTIFYING BY AFFIDAVIT THAT THIS
 TRUSS LAYOUT AND ATTACHMENT SHALL MEET
 ALL THE REQUIREMENTS OF THIS CODE.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X 8412