2002-02-21 00:00:00BUILDING PLAN REVIEW
 PLAN REVIEW # 01110408
 SITE AMENITITES
  
 SBC= 1997 STANDARD BUILDING CODE
  
 BATH HOUSE
  
 1) SBC1804.2.7.2(3) MISSING SOILS REPORT
 2)- MISSING PRODUCT TESTING REPORTS FOR
 WINDOWS,DOORS (SWING & OVERHEAD)
 3)- THE TRUSS & GIRDER LAYOUT DOES NOT
 INDICATE THE UPLIFT LOADS THAT THE
 ANCHORS SHALL BE REQUIRED TO RESIST.THE
 ANCHOR SCHEDULE GIVES WHAT THE ANCHOR
 WILL BE ABLE TO RESIST!
  
 TRASH COMPACTOR
 COMMENTS FROM PREVIOUS REVIEWS COMPLETED
  
 REMOTE GARAGE PLAN
 1)- SBC 1804.2.7.2(3) SOIL REPORT/
 W MINIMUM BEARING VALUE.
 2)- DESIGN PERAMETERS, OPEN, PARTIALLY
 OPEN? NO INDICATION
 3)- WHAT WILL THE USAGE BE FOR THE OPEN
 HALF? CARWASH?
 4)- AGAIN THE TRUSSES DO NOT GIVE THE
 UPLIFT VALUES, ONLY AN ANCHOR SCHEDULE?
 5)- SBC1606.2.6.2 COMPONENTS & CLADDING
 3 COPIES OF PRODUCT APPROVALS, SBCCI OR
 DADE COUNTY PRODUCT TESTING REPORTS.
 FOR WINDOWS, DOORS (SWING & OVERHEAD)
 AS WELL AS ROOFING MATERIALS.
 6)- PLANS ARE TO BE SUBMITTED TO COUNTY
 BUILDING DEPT FOR ASSESSMENT FOR COUNTY
 IMPACT FEES.
 RADON FEES TO BE COLLECTED BY CITY FOR
 STATE.
 PROJECT SHALL REQUIRE A RESIDENT INSPECT
 OR, SEE DON NEELY BEFORE PERMIT CAN
 BE ISSUED.