Plan Review Notes
Plan Review Notes For Permit 01110408
Permit Number 01110408
Review Stop B
Sequence Number 1
Notes
Date Text
2001-12-08 00:00:00BUILDING PLAN REVIEW
 PLAN REVIEW# 01110408
 ADDRESS: TO BE DETERMINED
 VILLAGE WEST LUXURY APARTMENTS
 PARCEL "D" PHASE I
 OWN: EPOCH PROPERTIES
 TEL (407) 644-9055
 FAX (407) 644-9845
  
 PLAN REVIEW WILL BE COMPLETED UNDER THE
 1997 STANDARD BUILDING CODE.
  
 SITE AMENITIES: A CLEAR SITE PLAN SHALL
 BE REQUIRED DESCRIBING THE TYPES OF
 BUILDINGS, POOLS, CABANAS, THE GATE
 HOUSE, SITE WALLS OR FENCES, SIGNAGE
 AND DUMPSTER LOCATION.
  
 FAIR HOUSING ACT REQUIRES AN ACCESSIBLE
 ROUTE FROM THE PUBLIC TRANSPORTATION
 STOP, THIS ACCESSIBLE ROUTE SHALL
 CONNECT BUILDINGS ALL COMMON ELEMENTS,
 SPACES & ELEMENTS. INDICATE WHERE THE
 MAIL CENTERS WILL BE & AND A CONTINIOUS
 PATH.
  
 PHASE I TO PHASE II WILL THERE BE 2 DIF-
 FERENT PROJECT NAMES & ADDRESSES?
  
 BATH HOUSE
 A2.51/S1 BATH HOUSE PLANS DO NOT GIVE
 THE FLOOR & WALL FINISHES REQUIRED SBC
 1204.2 PUBLIC RESTROOMS, WALLS & FLOORS
 OF ALL PUBLIC RESTROOMS SHALL BE LINED
 WITH AN NONABSORBANT MATERIAL TO A
 HEIGTH OF 4'-0" ABOVE THE FLOOR.
  
 FLOOR FINISH, FAIR HOUS. ANSI TECH
 REQUIREMENTS A4.5 GROUND & FLOOR SURFACE
 REQUIRE A STATIC COEFICIENT OF FRICTION
 OF 0.6 FOR ACCESSIBLE ROUTES AND 0.8
 FOR RAMPS.
  
 SOILS TREATMENT PLANS INDICATE A TERMITE
 PRETREATMENT BEFORE PLACEMENT OF CON-
 CRETE BUT NEGLETE SECTION SBC 1814.3.3
 1814.3.3 DAMPPROOFING OF SLAB.
  
 THE ARCH. NOR STRUCTURAL PLANS DO NOT
 INDICATE THE BASIC WIND VELOCITY
 PRESSURE, NOR MEAN ROOF HEIGTH.
  
 MISSING SBC 1804.2.7.2(3) SOILS REPORT
 GIVING THE MINIMUM SAFE BEARING VALUE
  
 NOTE: ACTUAL DESIGN PRESSURES FOR ALL EX
 TERIOR WINDOWS, DOORS, GARAGE DOORS AND
 SIMILAR ENVELOPE ELEMENTS MUST BE INDICA
 TED ON CONSTRUCTION PLANS (ELEVATION).
  
 PRODUCT APPROVALS: PRODUCT APPROVALS
 SHALL BE REQUIRED (3 COPIES RESIDENET
 INSPECTOR PROGRAM) FOR ALL OPENINGS OF
 THE EXTERIOR ENVELOPE, SEE CITIES
 STANDARD FOR IMPLEMENTATION FOR HURRI-
 CANE MISSLE IMPACT PROTECTION.SBCCI OR
 DADE COUNTY REPORTS. BUCK ATTACHMENT!
  
 ROOF ASSEMBLIES SHALL REQUIRE PRODUCT
 TESTING BY AN APPROVED TESTING AGENCY.
  
 GENERAL NOTES S1.11 :
 1) REMOVE NOTES ABOUT NORTH CAROLINA
 AMENDMENTS.
 2) FOUNDATIONS SOILS REPORT REQUIRED
 3) SBC 1804.1.3 MINIMUM FOUNDATION
 DEPTH BOTTOM OF FOUNDATION MINIMUM OF
 12" BELOW GRADE.
  
 TRUSS & GIRDER LAYOUT DOESN"T INDICATE
 THE VERTICAL, HORIZONTAL NOR GRAVITY
 LOADS IMPOSED, KNEE WALL SHALL REQUIRE
 A DETAIL SHOWING CONTINIOUS LOADING.
 HURRICANE ANCHOR SCHEDULE DOESN'T INDICA
 TE THE LOCATION OF THE ANCHOR TO BE USED
  
  
 TRASH COMPACTOR:
  
 RAMP SHALL COMPLY WITH FAIR HOUSING
 ANSI 4.8 RAMPS ABOVE 30" REQUIRE AN
 INTERMEDIATE LANDING.
  
 THE RAMP THAT A HANDICAPPED PERSON
 WOULD USE, WHAT STOPS THE PRSON FROM
 GOING OVER THE EDGE?
  
 GAURDHOUSE
 IS THIS STUCTURE HANDICAPPED ACCESSIBLE?
 THERE ARE NO RESTROOM FACILITIES?
 PRODUCT APPROVALS REQUIRED.
 TRUSS LAYOUT WITH ANCHOR SCHEDULE & THE
 LOADS TO BE REISTED.
 ROOFING REPORTS MISSING.
  
 REMOTE GARAGE PLAN:
 THE PREVIOUS COMMENTS FROM THE BATH
 HOUSE ARE IN AFFECT. SOILS REPORT,
 DAMP PROOFING, PRODUCT APPROVALS,
 DESIGN PRESSURES TO BE INDICATED ON PLAN
 MISSING INFORMATION AS TO TRUSS TIE
 DOWN.
 HOW IS THIS BUILDING DESIGNED? SCLOSED,
 PARTIALLY OPEN OR OPEN? USE FACTOR?
 SBC AMENDMENT 1606.4.2 EXCEPTION(6).
  
 WHAT IS THE ACTUAL USAGE OF THIS BUILD-
 ING, IS HALF OF THE BUILDING TO BE A
 CAR WASH?
  
 THE INTERIOR FINISH NOT GIVEN, WALLS
 & CEILING?
  
 THE ENCLOSED SECTION OF THIS STRUCTURE
 DOES NOT MEET THE EGRESS REQUIREMENTS
 OF 1012.1.1.
  
 PLANS ARE NOT INCLUDED INDICATING FRONT
 ENTRY GATES, WIDTH OF OPENINGS.PHASE 1
 TO PHASE II, WILL THERE BE A CONTINIOUS
 ROAD BETWEEN THE 2 PHASES?
  
 BEFORE ISSUANCE OF PERMIT,CONTRACTOR
 SHALL HAVE PLANS ASSESSED FOR COUNTY
 IMPACT FEES, COUNTY BUILDING DEPARTMENT
  
 STATE RADON FEES TO BE PAID TO CITY
 AT TIME OF ISSUANCE @ $.01 SQ.FT.
  
 THIS SITE SHALL REQUIRE A RESIDENT IN-
 SPECTOR, A MEETING WITH ASSISTANT BUILD-
 ING OFFICIAL DON NEELY SHALL BE REQUIRED
 TO REGISTER THE COMPANY & INSPECTOR.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X8412