Plan Review Notes
Plan Review Notes For Permit 01110407
Permit Number 01110407
Review Stop E
Sequence Number 7
Notes
Date Text
2002-08-09 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATIONAND RESUBMIT FOR REVIEW:
  
 1} PLEASE NOTE THAT ON THE PREVIOUS SIX
 REVIEWS THE SERVICE WAS 3 PHASE AND ON
 THIS REVIEW IT IS SINGLE PHASE,PLEASE
 VERIFY THAT ALL THE EQUIPMENT IS BEING
 CHANGED TO SINGLE PHASE.THE MECHANICAL
 DRAWINGS NEED TO BE RESUBMITTED TO
 REFLECT THESE CHANGES AND ALSO TO SHOW
 THE LOCATIONS AND CALCULATIONS OF THE
 THREE UNITS BEING ADDED.
  
 2} THE AIC RATINGS REMAINED THE SAME
 FROM THE 3 PHASE CALCULATION TO THE
 SINGLE PHASE CALCULATIONS,PLEASE
 RECALCULATE.
  
 3} PANELS "A" & "B" ARE LISTED AT 208
 VOLTS AND THE SERVICE IS SHOWN AS
 240V,PLEASE CLARIFY.
  
 4} PANEL "B" IS LISTED AS A 100 AMP
 PANEL BUT IS CALCULATED WITH A 142 AMP
 LOAD,PLEASE CLARIFY.
  
 5} PANEL "B" FEEDERS ARE SHOWN AS BEING
 PROTECTED BY 150 AMP OCP,SEE NOTE #4.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392