Plan Review Notes
Plan Review Notes For Permit 01110407
Permit Number 01110407
Review Stop E
Sequence Number 6
Notes
Date Text
2002-07-18 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT EQUIPMNET
 GROUNDING CONDUCTORS ARE BEING SHOWN
 BETWEEN GUTTER AND FIRST MEANS OF DSIC?
 PLEASE NOTE THIS A PARALLELING THE
 NEUTRAL, WHICH IS NOT PERMITTED.
 PLEASE NOTE THAT EQUIPMENT GRNDS ONLY
 GET INSTALLED AFTER THE FIRST MEANS
 OF DISC, DUE TO THE FACT THAT THE
 NEUTRAL IS BONDED AT THAT LOCATION.
  
 2)NOTE: PLEASE NOTE, A NEW PANEL IS
 BEING ADDED AND IS NOT SHOWN BEING ADDED
 TO CLUBHOUSE LOAD CALCULATION.??
 PLEASE NOTE THAT PER LOAD CALCUALTIONS,
 THIS NEW LOAD WOULD PUT SERVICE WAY OVER
 SERVICE ENTRANCE CONDUCTOR SIZES>>>
 PLEASE NOTE THAT LOAD SHOWN FOR PANEL
 "D" DOES NOT CORRELATE WITH LOAD ON
 PANEL SCHEDULE LOAD.
  
 3)NOTE: PLEASE CLARFIY CONDUCTORS,
 PANELS ARE SHOWN AS 3-PHASE AND # OF
 CONDUCTORS DO NOT SEEM TO CORRELATE.
 PLEASE GIVE A MORE DETAIL BREAKDOWN OF
 "CIRCLE" DETAILS ON RISER DIAGRAM.
 3PH4W??
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372