| 2002-07-18 00:00:00 | *************** UNSAT **************** |
| | |
| | 1)NOTE: PLEASE NOTE THAT EQUIPMNET |
| | GROUNDING CONDUCTORS ARE BEING SHOWN |
| | BETWEEN GUTTER AND FIRST MEANS OF DSIC? |
| | PLEASE NOTE THIS A PARALLELING THE |
| | NEUTRAL, WHICH IS NOT PERMITTED. |
| | PLEASE NOTE THAT EQUIPMENT GRNDS ONLY |
| | GET INSTALLED AFTER THE FIRST MEANS |
| | OF DISC, DUE TO THE FACT THAT THE |
| | NEUTRAL IS BONDED AT THAT LOCATION. |
| | |
| | 2)NOTE: PLEASE NOTE, A NEW PANEL IS |
| | BEING ADDED AND IS NOT SHOWN BEING ADDED |
| | TO CLUBHOUSE LOAD CALCULATION.?? |
| | PLEASE NOTE THAT PER LOAD CALCUALTIONS, |
| | THIS NEW LOAD WOULD PUT SERVICE WAY OVER |
| | SERVICE ENTRANCE CONDUCTOR SIZES>>> |
| | PLEASE NOTE THAT LOAD SHOWN FOR PANEL |
| | "D" DOES NOT CORRELATE WITH LOAD ON |
| | PANEL SCHEDULE LOAD. |
| | |
| | 3)NOTE: PLEASE CLARFIY CONDUCTORS, |
| | PANELS ARE SHOWN AS 3-PHASE AND # OF |
| | CONDUCTORS DO NOT SEEM TO CORRELATE. |
| | PLEASE GIVE A MORE DETAIL BREAKDOWN OF |
| | "CIRCLE" DETAILS ON RISER DIAGRAM. |
| | 3PH4W?? |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |