| 2002-03-26 00:00:00 | BUILDING PLAN REVIEW |
| | PLAN REVIEW # 01110409 |
| | BRIGER TRACT "D" |
| | BUILDING TYPE I |
| | THIRD REVIEW |
| | |
| | SBC= 1997 STANDARD BUILDING REVIEW |
| | |
| | 1)- SBC 1804.1.8THE AREA UNDER FOOTING |
| | FOUNDATIONS, CONRETE SLABS ON GRADE |
| | SHALL HAVE ALL VEGETATION AND FOREIGN |
| | MATERIALS REMOVED PRIOR TO THEIR CON- |
| | STRUCTION.THE TEST BORING B-1 INDICATES |
| | THAT IN THE UPPER ZONE AN ORGANIC CON- |
| | TENT OF 10% WAS FOUND. PRIOR TO BUILDING |
| | FURTHER TESTING AND REMOVAL SHALL BE |
| | REQUIRED BEFORE BUILDING PAD CAN BE DEVE |
| | LOPED. AS PER SOILS REPORT. |
| | |
| | 2)- SBC 1606.2.6.2 COMPONENTS & CLADDING |
| | THREE COPIES OF ALL PRODUCT ACCEPTANCE |
| | TESTING REPORTS SHALL BE REQUIRED FOR |
| | ALL GLAZED OPENINGS, EXT DOORS,SKYLIGHTS |
| | GLASS BLOCK, STORM SHUTTERS AND ROOFING |
| | ASSEMBLIES. WHEN PRODUCT TESTING REPORTS |
| | ARE NOT FILED WITH THE PLANS AND THE |
| | BUILDING IS APPROVED, THE STIPULATION |
| | THAT A SEPERATE PERMIT WITH ASSOCIATED |
| | FEES SHALL BE REQUIRED, ALSO THE CITIES |
| | GUIDELINE FOR LARGE PROJECTS REGARDING |
| | PROTECTION FOR ALL GLAZED OPENINGS |
| | SHALL BE ADHERED TO, SEE ATTACHED GUIDE- |
| | LINES. THE BUILDING OFFICIAL SHALL |
| | REVIEW AND APPROVE ALL PROPOSED PRE- |
| | STORM PREPERATION PLANS. |
| | |
| | 3)-SHEET S-D1.1 INDICATES A COLUMN |
| | DETAIL MISSING INFO FOR WELDS. |
| | |
| | 4)- RESIDENT INSPECTOR REQUIRED, SEE |
| | ASSIS. BUILD. OFF. DON NEELY FOR INFORMA |
| | TION. |
| | 5)- COUNTY IMPACT FEES TO BE PAID, CON- |
| | TRACTOR TO SUBMIT PLANS TO COUNTY FOR |
| | ASSESSMENT. |
| | CONTTRACTOR TO PAY RADON FEES AT TIME OF |
| | ISSUANCE. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |