Plan Review Notes
Plan Review Notes For Permit 01110407
Permit Number 01110407
Review Stop P
Sequence Number 3
Notes
Date Text
2002-03-18 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) FROM PREVIOUS REVIEWS, SHT A7.61 DE-
 TAIL #10 BAR SINK. DETAIL DOES NOT COM-
 PLY WITH FACBC SEC 4.24. COUNTER HEIGTH
 SHALL BE 2'10" NOT 3'0" AS SHOWN. SEC
 4.24.2. KNEE CLEARANCE NOT SHOWN, SEC
 4.24.3. CLEAR FLOOR SPACE NOT SHOWN, SEC
 4.24.5.
 2) FROM PREVIOUS REVIEW, SHT A7.61 DE-
 TAILS #8 & #9, PLEASE SHOW CLEAR FLOOR
 SPACE. LAV TO BE CENTERED ON CLEAR FLOOR
 SPACE MINIMUM OF 15" OFF WALL TO CENTER.
 3) FROM PREVIOUS REVIEW, SHT A7.61 DE-
 TAILS #8 & #9 DOORS SHALL NOT SWING INTO
 CLEAR FLOOR SPACE OF ANY FIXTURE, SEC
 4.17.5 & 4.22.2 OR THE TURNING RADIUS
 SEC 4.22.3.
 4) FROM PREVIOUS REVIEW, PLEASE SHOW
 CLEAR FLOOR SPACE FOR ALL HDCP FIXTURES.
 SHT A7.61
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377