| Plan Review Notes For Permit 01110407 |
| Permit Number |
01110407 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-03-27 00:00:00 | A) CIVIL DRAWINGS INDICATING FIRE MAIN | | | LOCATIONS, SIZES, AND FIRE HYDRANT | | | LOCATIONS NOT YET BEEN APPROVED. | | | B) SIX INCH UNDERGROUND PIPE TO | | | MECHANICAL ROOMSTILL SHOWN RUN | | | UNDERNEATH PORTIONS OF THE BUILDING. | | | C) FIRE DEPARTMENT CONNECTION NOT SHOWN | | | ON FIRE SPRINKLER PLANS. | | | D) BUILDING ADDRESS REQUIRED ON BUILDING | | | E) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|